Section-2 Installation
October 28, 2013
2
‐
10
Copyright
©2013,
Harris
Broadcast
WARNING:
Disconnect
primary
power
prior
to
servicing.
888
‐
2720
‐
001
Note
This chart is correct for all FAX models with or without AC Distribution Panel.
Please
read
all
the
following
Warnings
and
Cautions
prior
to
preceding
with
this
section.
Warning
DISABLE AND LOCK OUT STATION PRIMARY POWER BEFORE PRIMARY POWER CABLES
ARE CONNECTED TO THE EQUIPMENT.
Caution
CHECK THE AC POWER FEEDING THE FAX. IT MUST BE WITHIN THE VOLTAGE RANGES
SPECIFIED ON THE MAINS INTERCONNECT WIRING DIAGRAM Table 2-2. ANY VOLTAGE
OUTSIDE THIS RANGE WILL CAUSE DAMAGE TO THE EQUIPMENT. THE VOLTAGE SHOULD
BE MEASURED LINE TO LINE, AND IF A NEUTRAL IS USED, LINE TO NEUTRAL.
Warning
AN EXTERNAL CIRCUIT PROTECTION DEVICE (BREAKER OR FUSE) IS REQUIRED FOR
EACH AC LINE INPUT. THIS IS PROVIDED BY THE CUSTOMER IN ACCORDANCE WITH THE
AC INTERCONNECT DRAWING OR BY HARRIS BROADCAST IF AN IN-RACK AC DISTRIBU-
TION CHASSIS IS PURCHASED (OPTIONAL). IN THE LATTER CASE, AN EXTERNAL CIRCUIT
PROTECTION DEVICE TO HANDLE THE ENTIRE TRANSMITTER LOAD AT THE MAIN AC DIS-
TRIBUTION POINT IS STILL REQUIRED, IN ACCORDANCE WITH PREVAILING LOCAL SAFETY
NORMS.
Warning
THE NEUTRAL WIRE SHOULD NOT GO THROUGH THE EXTERNAL BREAKER.
2.10.1
AC Connection without Distribution Panel
AC
power
is
connected
to
the
stand
‐
alone
FAX
or
to
a
cabinet
that
does
not
contain
a
Harris
Broadcast
supplied
AC
Distribution
Panel
by
running
the
AC
power
wires
through
the
AC
Mains
input
hole
provided
on
the
upper
right
rear
corner
of
the
transmitter.
See
Figure
2
‐
7,
the
wires
can
go
in
the
top
as
shown
or
the
white
hole
plug
can
be
removed
and
the
wires
can
be
fed
through
there.
190
‐
264
VAC
Delta
L1,L2,L3,GND
Set
straps
for
Delta
190
‐
264
VAC
Wye
L1,L2,L3,GND
TX
will
be
strapped
for
Delta
and
no
Neutral
required.
Neutral
bar
will
not
be
installed.
330
‐
460
VAC
Wye
L1,L2,L3,Neu,GND
Transmitter
will
be
strapped
for
WYE
and
Neutral
required
Table 2-2 AC Mains Connection Chart (See 843-5614-482)
Voltage
Service
Connections