7
3-90-07205R26_10/14
Assembly
Boiler Kit Materials: (Refer to
“Parts Locations”
section
in this manual)
List of items contained within the boiler kit shipped with the
unit.
1 - Control board cover
1 - Access cover (Hopper Swing Plate Knob)
5 - Spring Handles
1 - 3/4” Boiler Drain
1 - 3/4” Safety Relief Valve
1 - 1/2” Aquastat Well
1 - 1/2” Dual Temperature/Pressure Gauge
1 - 100 ft. Sensor Cable (Outdoor Air Sensor)
1 - Outdoor Air Sensor
1 - Flue Tunnel Weldment
1 - Combustion Blower Assembly
1 - Heat Shield (Comb. Blower)
2 - UY Connectors
2 - Terminals 1/4 Female
1 - #8 X 1/2” TEK
3 - 1/4-20 X 5/8” Wing Screw
4 - 1/4” Lock Washer
4 - 1/4-20 Nuts
Installation of the Flue Tunnel Weldment, Combustion
Blower and Wiring, eSP and Heat Shield:
Step 1: First install the flue tunnel weldment by aligning the
(4) studs with the (4) holes in the ash chamber base. Fasten
the (4) nuts and lock washers provided, to the studs by
removing the access cover on the secondary ash chamber.
Step 2: Place the combustion motor onto the flue tunnel
weldment and tighten the (3) wing screws provided.
Step 3: Insert the Exhaust Sensing Probe (ESP) into the 1/8”
hole provided on the flue pipe stub. Fasten with the (1) #8 x
1/2” TEK screw also provided. ESP will be taped to the sheet
metal jacket for shipping purposes.
Step 4: Connect the flex conduit 90° elbow(Not Shown) to
the heat shield in the hole provided. Then connect the (3)
wires from the combustion blower with the (3) wires in the
flex conduit by using the push-on connectors and matching
the wire colors as follows: Red to Black, White to White and
Green to Green.
Step 5: Place Heat Shield over combustion blower and align
the swell latches with the holes in the sheet metal and tighten.
Heat Shield
NOTE: Refer to Fig’s 22, 23, and 24 located in this manual.
Flue Tunnel Weldment
ESP
Combustion Blower
Summary of Contents for PB 105
Page 51: ...3 90 07205R26_10 14...