8

P68 Pellet Stove

venting

requirements for terminating the venting

WARNING: Venting terminals must not be recessed 

into a wall or siding.

NOTE: Only PL vent pipe wall pass-throughs and fire 

stops should be used when venting through combustible 

materials.

NOTE: Always  take  into  consideration  the  effects 

of the prevailing wind direction or other wind currents 

that may cause flyash and/or smoke when placing the 

termination vent.

in addition, the following must be observed:

A. The clearance above grade  must be a minimum 

of 18".

1

B. The clearance to a window or door that may be 

opened must be a minimum of 48" to the side, 48" below 

the window/door, and 12" above the window/door.

1

with outside air installed, 18” 

)

C. A 12"  clearance to a permanently closed window  

is    recommended  to  prevent  condensation  on  the 

window.

D. The vertical clearance to a ventilated soffit located 

above the terminal within a horizontal distance of 2 feet 

(60 cm) from the center-line of the terminal  must be a 

minimum of 18".

E. The clearance to an unventilated soffit  must be 

a minimum of 12".

F. The clearance to an outside corner is 11" from 

center of pipe.

G. The clearance to an inside corner is 12".

H.  A vent must not be installed within 3 feet (90 cm) 

above a gas meter/regulator assembly when measured 

from the horizontal center-line of the regulator.

1

I. The clearance to service regulator vent outlet must 

be a minimum of 6 feet.

1

J. The clearance to a non-mechanical air supply inlet 

to the building or the combustion air inlet to any other 

appliance must be a minimum of 48”.

1

K. The clearance to a mechanical air supply inlet must 

be a minimum of 10 feet.

1

(

with outside air installed, 6 feet 

)

L. The clearance above a paved sidewalk or a paved 

driveway located on public property must be a minimum 

of  7 feet.

1,2

M. The clearance under a veranda, porch, deck or 

balcony must be a minimum of 12 inches.

1,3

(See b.)

NOTE:  The clearance to vegetation and other exterior 

combustibles such as mulch is 36” as measured from 

the center of the outlet or cap. This 36” radius continues 

to grade or a minimum of 7 feet below the outlet.

1

Certain Canadian and or  Local codes or regulations 

may require different clearances.

2

A  vent  shall  not  terminate  directly  above  a  side-

walk or paved driveway which is located between two 

single  family dwellings and serves both dwellings.

3

Only permitted if veranda, porch, deck, or balcony is 

fully open on a minimum of  2 sides beneath the floor.

note: Where passage through a wall, or partition of 

combustible construction is desired, the installation 

shall conform to can/cSa-b365. (if in  canada)

= Vent terminal

v

Summary of Contents for P68

Page 1: ...A SUITABLE FOR INSTALLATION IN MOBILE HOMES IF THIS pellet STOVE IS NOT PROPERLY INSTALLED A HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIA...

Page 2: ......

Page 3: ...sp ci ques locales concernant les pr cautions requises lors de la travers e d un mur ou d un plafond Contr ler et nettoyer fr quemment tout le systeme d evacuation des fum es conform ment aux recomma...

Page 4: ...stove design technology and manufacturing This 68 000 BTU stove has the highest output smartest controls widest heating range and minimal maintenance The P68 s huge output is managed by a microproces...

Page 5: ...ating season and at the end of each winter for the stove to work efficiently See cleaning instructions on page 23 Mobile Manufactured Home Standards Do Not Allow Installation In Rooms Designated For S...

Page 6: ...above the burnpot Flame Guide Install the cast iron flame guide on top of the burn pot Make sure that the flame guide is fully seated on the vertical sides of the burn pot and that the back of the gui...

Page 7: ...check for possible restrictions or the need for outside air see page 10 For more information on the draft test procedure refer to Page 21 Mobile Home Installation When installing this unit in a mobile...

Page 8: ...hin 3 feet 90 cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J...

Page 9: ...is not achieved For this reason and the fact that the P68 operates with a positive vent pressure we specify that the joints also be sealed with high temp RTV silicone Aluminum tape can also be used f...

Page 10: ...he flue outlet is more than 12 from the inlet cover The maximum length run of this pipe is 15 feet If a longer run is needed the size must be increased to 3 Inlet cover part number 1 10 08542 should b...

Page 11: ...throughs 1 Preferred method This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall Two inches from the wall is safe however four inches a...

Page 12: ...draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in method 6 The chimney should be inspected and cleaned before installing your stove I...

Page 13: ...used by the manufacturer Pipe size should be increased to 4 using this method Chimney must be of a type suitable for use with solid fuel 7 Installing into an existing chimney This method provides exce...

Page 14: ...ell in the room in the event of power failure Min above ground level 18 Venting Fig 15 Fig 14 PL vent manufacturer s firestop spacer and support See Page 7 for corner installation clearances Storm col...

Page 15: ...lect either Auto or Manual modes for the igniter using the igniter toggle switch When the toggle switch is in the Auto position the igniter located inside the burn pot is ready to automatically light...

Page 16: ...and smoke will escape through window and door gaskets When the igniter toggle switch is set to manual in this mode the distribution blower will not turn on with a temperature dial setting from 1 to 5...

Page 17: ...n to Stove Mode and put the fan on H Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes and check ash on front of burn pot Fig 18 If the ash line is larger than 1 turn the feed...

Page 18: ...e The advantage of this mode is to allow the operator to have a large viewing fire without blowing extra heat into the room During operation with the temperature dial set at 4 or less the distribution...

Page 19: ...r 30 minutes of burn time and check again If at 6 setting a 1 or less ash bed is not obtainable it is not a problem The 1 ash bed is only at maximum burn rate and at most normal settings the ash bed w...

Page 20: ...icate errors listed below Indicates power to distribution blower Status light error messages 3 Blinks Indicates an incomplete ESP circuit or that the ESP Exhaust Sensing Probe Has gone out of range a...

Page 21: ...to operate Combustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation Fig 22 Fig 23 A simple draft te...

Page 22: ...room air being drawn into the distribution fan NOTE Distances of more than 25 feet from the unit or in another room are not recommended The room sensor is essential for the P68 s excellent efficiency...

Page 23: ...is cold and shut down when removing ash pan 1 Pull on latch handle and remove ash pan Use ash pan handle to carry and dispose of ashes 2 Slide the ash pan back into the stove and latch the door by pu...

Page 24: ...out plate Latch open with blower cover partly removed Burn pot clean out is open Latch closed with blower cover in place Burn pot clean out is closed Fig 29 Fig 28 ESP Probe 5 Open burn pot clean out...

Page 25: ...lated male female wire connectors These connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the inside rear of the...

Page 26: ...the gasket channel should be free of all loose particles The gasket cement used to hold the gasket in place is RTV HIGH TEMPERATURE silicone Put a bead of RTV silicone in the bottom of the gasket chan...

Page 27: ...tainers and screws Apply the gasket material to the face of the new glass Lay the glass into the door making sure that the glass is contained within the channels and raised areas of the door itself La...

Page 28: ...el in hopper 2 Draft is too low blocked flue 3 Something is restricting fuel flow 4 Hopper lid not closed properly 5 Feed motor or combustion blower has failed SMOKE IS VISIBLE COMING OUT OF VENT 1 Ai...

Page 29: ...tends to cool the appliance thus robbing heat from your home Damp pellet fuel could turn back into sawdust which does not flow properly through the feed system Size Pellets are either 1 4 inch or 5 1...

Page 30: ...auge steel This is the minimum size for floor protection with this unit Part 1 00 06727 Hopper Extension The hopper extension allows you to put more pellet fuel in the hopper and extends burn time on...

Page 31: ...for samples The Brushed Stainless deer cutout pictured below is another option available This cutout reveals the color of the stove through the cut out shapes On the rear of the stove hopper there is...

Page 32: ...UND P O W E R C O R D 1 8 3 R U B B E R C O R D WHITE GREEN BLUE GREEN WHITE RED MALE FEMALE CONNECTIONS BROWN WHITE N O CONTACTS MALE FEMALE CONNECTIONS LT BLUE LT BLUE INSIDE BURNPOT IGNITER ELEMENT...

Page 33: ...o 2 or 3 Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed of...

Page 34: ...continued operation Your appliance will recognize when power is restored What happens depends on ESP temperature and whether it is equipped with automatic ignition in automatic setting units equipped...

Page 35: ...home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occ...

Page 36: ...as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ...42 P68 Pellet Stove Service Maintenance Log...

Page 43: ......

Page 44: ...00 Recycled Paper At Harman we build each product to a standard not a price Signature of Boxer Your premium quality hearth product designed and assembled by the experienced and skilled members at Harm...

Reviews: