11
P68 Pellet Stove
#2 Preferred method
This method also provides excellent venting
for normal operation but requires the stove to be
installed farther from the wall. The vertical portion of
the vent should be three to five feet high and at least
three inches from a combustible wall. This vertical
section will provide natural draft in the event of a
power failure.
If the stove is installed below grade be sure the
vent te
rmination is at least 18" above grade. The
outlet must also be 1 foot from the house/building.
Note: Do not place joints within wall pass-
throughs.
#1 Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed closest
to the wall. Two inches from the wall is safe; however,
four inches allows better access to remove the rear
panel. The vertical portion of the vent should be three
to five feet high. This vertical section will help provide
natural draft in the event of a power failure.
note: do
not place joints within wall pass-throughs.
venting
36" min
clearance to any
combustible
material
12" min. wall to outlet
caution
Keep combustible materials (such as grass,
leaves, etc.) at least 3 feet away from the flue
outlet on the outside of the building
Fig. 8
3 ft.
to
combustibles
3 ft.
to combustibles
Fig. 9
3 ft.
to
combustibles
3 ft.
to combustibles