background image

8

APM-001e 
AUG 2015

SOLENOID VALVES

The APM is equipped with four solenoid valves.  These are: 

the liquid drainer solenoid valve (A), the liquid line solenoid 
valve (B), the purge gas solenoid valve (C), and the water 
solenoid valve (D). See Figure 11. With the exception of the 
water solenoid valve, each is directly welded in-line and 
has a stainless steel removable seat/orifice (see Figure 8).  

The removable seat/orifice facilitates easy access to the 

orifice for inspection or replacement.  If necessary, the 
water solenoid valve (D), whose brass body has threaded 
ends, can easily be replaced or parts thereof changed.

Figure 8

LIQUID DRAINER

The liquid drainer removes any condensed liquid that trickles 

from the foul gas line into the purger.  This enables the 
purger to always be condensing gas, rather than having 
liquid entering the condensing section of the purger and 
limiting proper operation.  The drainer solenoid valve (A) 
will open to empty a reasonable amount of excess liquid 
directly to the flooded evaporator.  However, if too much 
liquid comes down the foul gas line, due to improperly 
piped condensers, corrective action must be taken.  See 
the Foul gas piping section on page 3.  

STRAINER/ORIFICE

The strainer/orifice meters condensed liquid refrigerant 

from the high-pressure side of the purger into its flooded 
evaporator.  It features a dual filter arrangement to reduce 
potential orifice blockage.  This dual filter (strainer) removes 
particles and houses the integral orifice (strainer/orifice 
screen assembly).  See Figure 10.

In addition, separate remote point solenoid valves are 
required, one for each enabled purge point. These are not 
included with the APM. The Hansen type HS8 solenoid 
valve having a ½” (13mm) port and a stainless steel piston 
is recommended. Below is a typical purge point solenoid 
valve with close-coupled strainer (Figure 9).

Figure 9

 

REMOVABLE

SEAT/ORIFICE

CHECK VALVES

There are three check valves on the purger.  An 80 psid 

(5.5 bar) differential check valve is installed on the purge 
gas line to prevent any possibility of reverse flow of water 

into the purger.  A 225 psid (15.5 bar) differential relief 

check valve leads from the condensing coil inlet to the 
suction line; this prevents excessive purger pressure.  A 
third check valve is installed from the liquid drainer to the 
evaporator coil to prevent reverse flow with a temporary 

loss of foul gas pressure.

WATERTIGHT 
ENCAPSULATED 
COIL

STAINLESS 
STEEL PISTON

MANUAL OPENING 
STEM

CLOSE-COUPLED 
STRAINTER

REMOVABLE SEAT 
ORIFICE

WATER BUBBLER

The APM is equipped with a water bubbler which eliminates 

any water bottle attention.  Purge gas (noncondensibles) 
from the purger flows into the bottom of the water bubbler 
where residual ammonia can be absorbed into the water.  

The water with absorbed ammonia flows to a drain.  The 

water solenoid valve (D) opens to automatically replenish 
water to the bubbler each time the purge gas solenoid 
valve (C) energizes.  A 30-second delay keeps the water 
solenoid valve (D) open after the purge gas solenoid valve 
(C) de-energizes to refill water bubbler.  Proper release of 
noncondensibles through the bubbler is usually indicated 
by large, 1/2" (13mm) diameter bubbles.

STRAINER/ORIFICE

SCREEN ASSEMBLY

STRAINER/ORIFICE

BODY

STRAINER/ORIFICE 
BODY

STRAINER/ORIFICE 
SCREEN ASSEMBLY

SECTION 2   ELECTRICAL INSTALLATION & OPERATION

Figure 10

Summary of Contents for AUTO-PURGER M

Page 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Page 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Page 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Page 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Page 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Page 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Page 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Page 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Page 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Page 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Page 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Page 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Page 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Page 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Page 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Page 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...

Reviews:

Related manuals for AUTO-PURGER M