CAUTION

Hansen purgers are for refrigeration systems only. These 
instructions and related safety precautions must be read 
completely and understood before selecting, using, or 
servicing these purgers. Only knowledgeable, trained 
refrigeration technicians should install, operate, or 
service these purgers. Stated temperature and pressure 
limits should not be exceeded. Purger components 
should not be removed from the purger unless the system 
has been evacuated to zero pressure. See also the Safety 
Precautions in the current List Price schedule and the 
Safety Precautions Sheet supplied with this product. 
Escaping refrigerant can cause injury, especially to  
the eyes and lungs.

WARRANTY

Electrical and electronic components are guaranteed 
against defective materials and workmanship for 90 days 
F.O.B. our plant. All other components are guaranteed 
against defective materials or workmanship for one year 
F.O.B. our plant.  No consequential damages or field 
labor is included.

AUTO-PURGER APP 

AUTO-PURGER PLUS is a totally automatic, electronically 

controlled non-condensible gas (air) and water purger for 
reducing the energy costs 
of operating an ammonia 
r e f r i g e r a t i o n   s y s t e m . 
Shipped preassembled, 
prewired, insulated, and 

includes a n automatic 
water bubbler, a relief 
valve, and an isolation 
ser vice valve package. 

One AUTO-PURGER PLUS 

is typically sufficient for a 

1500 ton (5275 kW) system 

(or a 750 ton (2638 kW) 
systemoperating below 0 
psig (0bar g). All models 
suitable for ammonia only.

SELECTING AN AUTO-PURGER®

In addition to the AUTO-PURGER

®

 AP, Hansen 

Technologies offers three other versions—the 

compact AUTO-PURGER

®

 APM, the gas (air) and 

water AUTO-PURGER

®

 APP, and the Nonelectrical 

AUTO-PURGER

®

 (NEAP). Use the following 

descriptions to help select the best AUTO-PURGER 
for your needs. For additional assistance, contact the 
factory. 

AUTO-PURGER  AP

This is the original AUTO-PURGER. It has solid-state 

control and is ideal for larger systems, up to 1500 tons 
(5300 kW) ammonia. This is two to three times the 
air removal capacity of 
the Armstrong purger. 
With models available to 
purge up to 24 points, the 

AP features automatic 

start-up with electronic 
control. The purge cycles 
c a n   b e   i n d i v i d u a l l y 
adjusted to meet system 
requirements. The AP 
includes an automatic 
w a t e r   b u b b l e r .   A n 
optional NEMA 4 rated 
enclosure is available. 

AUTO-PURGER  APM

A more compact version of the original AP, the 
AUTO-PURGER APM is ideal for medium-size systems, 

up to 200 tons (700 kW). Like 
the AP, the APM features 
au to m a t i c  s t a r t- u p  w i t h 
electronic control. Designed 
for up to four purge points, an 
electronic “brain” searches 
for noncondensible gases 
in the system and purges 
at those points when air is 
present. The APM includes an 
automatic water bubbler and 
comes standard with a NEMA 

12,13 control cabinet. For use 

with ammonia refrigeration 
systems. Assembled, tested, 
and ready to run.

Nonelectrical AUTO-PURGER (NEAP)

T h e  n o n e l e c t r o n i c a l  AU TO -

PURGER (NEAP) is ideal for small  
systems, up to 100 tons (350 
kW). The nonelectronical design 
also makes the NEAP ideal for 
explosion proof applications. 

The simple design of the NEAP 

featur es ea sy s t a r t- up a nd 
is gener a lly use d to pur ge 
a single point. For use with 
ammonia refrigeration systems. 

Assembled, tested, and ready to 

run.

Hansen Auto-Purger Specifications 

Model 

AP 

APP 

APM 

NEAP 

Pressure Rating 

400 psig  400 psig  400 psig  400 psig 

Test Pressure 

450 psig  450 psig  450 psig  450 psig 

Min. Operating Temp. 

-60°F 

-60°F 

-60°F 

-60°F 

Max Operating Temp. 

240°F 

240°F 

240°F 

240°F 

Ammonia Charge 

11 lb 

14 lb 

7 lb 

7lb 

Cubic Volume 

0.5 ft

3

0.7 ft

3

 

0.3 ft

3

 

0.2 ft

3

 

Refr. Capacity (tons) 

1 TR 

1 TR 

0.5 TR 

0.5 TR 

Certification Type (std)  CRN, CSA  CRN, CSA  CRN, CSA 

CRN 

HEX Length x Width 

  

(to calculate relief size) 

48” x 5” 

48” x 5” 

18” x 5” 

14” x 5” 

Bulletin number 

AP003 

APP001  APM001  NEAP001 

Summary of Contents for AUTO-PURGER M

Page 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Page 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Page 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Page 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Page 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Page 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Page 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Page 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Page 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Page 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Page 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Page 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Page 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Page 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Page 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Page 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...

Reviews:

Related manuals for AUTO-PURGER M