Hansen AUTO-PURGER M Service Instructions Manual Download Page 7

7

APM-001e 

AUG 2015

ACTIVE PURGE POINT

The front of the control cabinet has lights which indicate 

the active purge point.  The active purge point can be 
manually advanced in any operational mode by pushing 
the purge point advance button.

PURGER STATUS LIGHTS

There are two purger status lights on the front of the control 

cabinet next to the digital readout. These are the Purging 
status light and Standby status light which indicate when 
noncondensible gas (air) is being released from the purger 
(Purging), or when the purger is in a waiting mode (Standby).

PURGING LOG

The purging log is displayed on the digital readout.  It 

displays the number of minutes the purge gas solenoid valve 
(C) (see Figure 11) has been open to release noncondensibles 

into the water bubbler. 

The purger log can be used to track the release of 

noncondensible gas.  If a daily or weekly record is kept, then 
any abnormal increases in the amount of noncondensible 
gases can be noted, and corrective measures can be taken.  
Little or no activity compared to normal operation may 
indicate noncondensibles have been thoroughly removed 
or a problem with the purger.  Frequent activity beyond 
normal could mean excessive new leakage of air into the 
system.  To reset the purge log, push the zero reset button 
next to the digital readout on the front panel.

DIAGNOSTIC FEATURES

Although the APM is very reliable, after an extended 

operation or under severe conditions, problems may 
occur or be suspected.  Under these conditions, due to 
the importance of the purging functions, restoration to 
normal operation is desired as quickly as possible.  The 

APM features diagnostic codes which are displayed on the 

digital readout when abnormal operation of the refrigeration 
system or the APM is detected.  These flashing numbers 

help to identify the problem area.  Below is a quick reference 
to these diagnostic codes.  The digital readout will display 
the diagnostic code related to the occurrence which first 
put the APM into this mode; exception, 6666 will override 

7777.  Also see the troubleshooting guide on page 10 for 

detailed explanation.

Flashing 2222  LOSS OF FOUL GAS PRESSURE.  

Flashing 3333  PURGER TOO WARM.

Flashing 4444   PURGED OVER 60 MINUTE TIME LIMIT.

Flashing 5555   PURGER SHUT-OFF REMOTELY.   

Flashing 6666   LEVEL CONTROL OUT OF RANGE.  

Flashing 7777   LOSS OF HIGH-PRESSURE LIQUID.  

PURGE POINT ENABLE SWITCHES

These switches are located on the control board and are 

all factory-set to the ON position.  They control whether 
or not a purge point can become active.  If for example, 
only three purge points are being utilized, the number 4 
purge point enable switch should be in the downward off 
position (see Figure 7).  By doing this, the unused purge 
point is disabled and purger time is not wasted. 

PUMP OUT PROCEDURE

Performing certain types of service on the APM may first 
require the purger to be pumped-out (drained of liquid 
refrigerant). To begin pump-out, shut off the foul gas 
and high-pressure liquid lines. Wait for all refrigerant to 
evaporate to suction; this usually takes several hours to 
complete. Using safe refrigeration practices, reduce the 
pressure to zero. In addition to following these procedures, 
check the lower portion of drainer and the APM piping for 
signs of frost. If there is no frost, pump-out is probably 
complete. If there is frost, this means excess refrigerant 
is still in the drainer and/or piping. To drain, energize the 
drainer solenoid valve.

To accelerate the pump out process, attach ammonia hoses 

to the oil drain valves. Close the main suction line to the 
purger. Using the oil drain valves, pump out to a lower 
suction pressure than the main purger suction line. When 
pumped out, close the oil drain valves and leave the main 
suction line closed to isolate the purger. With electricity 
on, the pressure in the purger should remain at zero. This 
process should be completed only by knowledgeable 
refrigeration technicians.

CONTROL BOARD

Figure 7

SECTION 2   ELECTRICAL INSTALLATION & OPERATION

Summary of Contents for AUTO-PURGER M

Page 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Page 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Page 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Page 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Page 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Page 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Page 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Page 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Page 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Page 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Page 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Page 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Page 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Page 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Page 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Page 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...

Reviews: