background image

2

APM-001e 
AUG 2015

further condensing of the saturated gas can occur.  If this 
cannot be avoided, the line must be insulated because 
flooded purge point lines result in flooding the APM with 
liquid, causing a temporary halt of noncondensibles 
being removed. If flooding can not be avoided, additional 
condensate drainage may be necessary. 

It is important that all purge points be located above any 
liquid surfaces to avoid drawing liquid refrigerant, rather 
than vapor, into the APM. 

EVAPORATIVE CONDENSER PIPING

Typically, evaporative condenser outlet liquid drain lines 

on each circuit must drop a minimum of 4 feet (1.2 m) for 
ammonia from the centerline of the evaporative condenser 
outlet to the centerline of highest elevation of the liquid 

line manifold to receiver.  Preferably, each circuit should 

have a P trap to balance variations in pressure drop in each 

circuit to prevent liquid from backing up into one or more 
condensers, and thereby flooding the purge point.  

Most air 

from the system will normally be trapped between the 

condenser and the P trap

.  Also, a properly-sized equalizer 

line from the receiver will help drain condenser circuits 
into the receiver.  Refer to ASHRAE GUIDELINES or IIAR 
Papers on condenser piping design.  Hansen Technologies 

can provide copies of these articles.  Also, consult the 
condenser manufacturers’ installation instructions for 
additional piping and sizing information.

On evaporative condensers, avoid using one purge point 
solenoid valve to purge two circuits.  This practice negates 

the P-trap on the condenser drain line because of the 
purge connections of the two circuits and may back liquid 
up into one circuit.

 

ACTIVE PURGE POINT
1

2

3

4

ENERGY SAVER

R

HANSEN TECHNOLOGIES

CORPORATION

(25)

(298)

ON HIGH PRESSURE CONDENSERS AND RECIEVERS

PROTECTED SUCTION ACCUMULATOR

(24)

(86)

(192)

TYPICAL

(16)

(508)

(813)

(152)

FOR POWER CONNECTION

FOR REMOTE PURGE POINT

SOLENOID VALVE CONNECTIONS

(86)

(359)

(49)

(457)

OIL DRAIN CONNECTION (3/8" FPT)

OIL DRAIN CONNECTION (3/8" FPT)

TYPICAL

(16)

(14)

MOUNTING HOLE

8 PLACES

(59)

(130)

(178)

SHUT-OFF VALVE CONNECTION

PRESSURE RELIEF VALVE

(406)

(464)

CONNECTION

1" PVC DRAIN

WALL OR COLUMN

18.25"

BUBBLER

CONTROL CABINET

1/2" CONNECTION FOR OPTIONAL

1/2" FPT WATER LINE

7.00"

3/4" SUCTION LINE

5.11"

0.53"      DIA

0.62"

18.00"

HIGH PRESSURE SEPARATOR

LOW PRESSURE SEPARATOR

1.93"

14.13"

3/4" CONDUIT KNOCK OUT

1/2" CONDUIT KNOCK OUT

6.00"

32.00"

20.00"

0.62"

3/4" SUCTION LINE CONNECTION TO

1/2" HIGH PRESSURE LIQUID LINE CONNECTION

1/2"   FOUL GAS'' LINE CONNECTION FROM PURGE POINTS

''

3.38"

16.00"

2.31"

1.00"

0.94"

3.38"

7.56"

11.75"

1.63" (41 MM)

INSTALLATION DIMENSIONS (MM)

Figure 1

FROM FOUL GAS SOURCE

CLOSE-COUPLED

ISOLATION

TO PURGER

1/2" (13 MM) PORT

SHUT-OFF VALVE

REMOTE PURGE POINT

SOLENOID VALVE

ISOLATION SHUT-OFF VALVE

STRAINER

(GLOBE VALVE STEM HORIZONTAL

IS PREFERRED)

LEVEL OR

PITCH DOWN

SECTION 1  MOUNTING & PIPING INSTALLATION

Summary of Contents for AUTO-PURGER M

Page 1: ...ore or after the purge point solenoid valves See Figure 2 The foul gas line should not pass through cold areas where INTRODUCTION The AUTO PURGER M is a compact and totally automatic electronically co...

Page 2: ...ndenser piping design Hansen Technologies can provide copies of these articles Also consult the condenser manufacturers installation instructions for additional piping and sizing information On evapor...

Page 3: ...E CLOSE COUPLED ISOLATION TO PURGER 1 2 13 MM PORT SHUT OFF VALVE REMOTE PURGE POINT SOLENOID VALVE ISOLATION SHUT OFF VALVE STRAINER GLOBE VALVE STEM HORIZONTAL IS PREFERRED LEVEL OR PITCH DOWN SECTI...

Page 4: ...oil will not be a problem unless the liquid line is connected to a vessel or line where oil can enter the purger See also the Caution section on page 14 Escaping refrigerant may cause personal injury...

Page 5: ...il voltage is different simply remove and discard the factory installed jumpers between terminals 13 14 and 15 16 Bring the purge point solenoid line L1 connection to terminal 14 and neutral L2 to ter...

Page 6: ...e gases that may have collected MANUAL OPERATION Manual Operation mode allows the operator to select one purge point continuously This is usually the case if a large volume of noncondensible gas is su...

Page 7: ...t will display the diagnostic code related to the occurrence which first put the APM into this mode exception 6666 will override 7777 Also see the troubleshooting guide on page 10 for detailed explana...

Page 8: ...d valves are required one for each enabled purge point These are not included with the APM The Hansen type HS8 solenoid valve having a 13mm port and a stainless steel piston is recommended Below is a...

Page 9: ...er diagnostic code 2222 flashes on the APM digital readout No purging of air will occur until foul gas pressure is restored OPERATION The foul gas may carry a certain amount of condensed refrigerant w...

Page 10: ...flooded evaporator is cooled down REASON 1 Suction temperature too high Check Verify the pressure at the purger suction line connection Action Connect to a lower temperature suction REASON 2 Restrict...

Page 11: ...ressure liquid available to maintain an adequate level in the flooded evaporator of the purger The purger will not purge air until this is corrected REASON 1 Liquid line solenoid valve B is not openin...

Page 12: ...to Piping Instructions in Section I of this bulletin Action Correct condenser and foul gas piping REASON 4 High side level sensor not detecting drop in liquid level due to oil Action Run recalibratio...

Page 13: ...QUID LINE SUCTION LINE 1 4 NPT 1 4 NPT SOCKET WELD SOCKET WELD SOCKET WELD VIEW ROTATED PIPE THREAD PIPE THREAD GAUGE VALVE GAUGE VALVE PURGER FRAME SHUT OFF VALVE VPM FOR CLARITY OPTIONAL VALVE PACKA...

Page 14: ...TIONAL VALVE PACKAGE VPMF The special construction for APMF AUTO PURGERs includes a filter dryer conditioning system for the foul gas and liquid line Water vapor as well as noncondensible gas may be p...

Page 15: ...20 1857 Temperature sensor 20 2303 High side level sensor 77 0796 Drainer and low side level sensor 77 0794 Solenoid coil kit 230V with DIN plug 70 1093 Solenoid coil kit 115V with DIN plug 70 1092 M...

Page 16: ...and the Nonelectrical AUTO PURGER NEAP Use the following descriptions to help select the best AUTO PURGER for your needs For additional assistance contact the factory AUTO PURGER AP This is the origin...