COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
28
15.3.2
�����~pacity (Stepless) Minimum (50-100%)
1. For new continuous (step less) capacity control system, Hanbell equipped all solenoid valves a Normally Closed.
If it is necessary to be equipped with other type solenoid valve, please specify it with MCS / Hanbell before order
confirmation.
Verify compressor load solenoid as Normally Open or Normally Closed.
2. If normally Open Solenoid, wire through the Normally Closed Relay Output.
3. If normally Closed Solenoid, wire through Normally Open Relay Output.
UNLOAD (NC)
LOAD (NC)
STRT UNLD (NC)
Start
Energize
Not energize
Energize
Loading
Not energize
Energize
Not energize
Unloading
Energize
Not energize
Not energize
Stable
Not energize
Not energize
Not energize
UNLOAD
LOAD
START UNLOAD