COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
21
1. Oil Charging: Only lubricants listed in Hanbell’s Technical Manual are to be used. NO SUBSTITUTES. Make sure the
oil level is to the middle of the high side sight glass, which is the terminal box side of the compressor. (For compressors
with internal oil separators)
2. Oil Heater: The heater needs to be energized for 24 hours prior to running the compressor and energized when the
compressor is off.
3. Make sure all valves are open (stop, angle valves with transducers, etc.)
4. Make sure all solenoids are wired correctly.
5. Make sure the motor module (INT69HBY) is wired correctly.
6. Make sure the electrical system is wired correctly and properly grounded.
7. Verify the controller is wired correctly. (Dry run)
Lubricant Charge
Model #
Oil Needed
(In Gallons)
RC2-100
1.9
RC2-140
1.9
RC2-170
1.9
RC2-180
1.9
RC2-200
2.1
RC2-230
3.7
RC2-260
3.7
RC2-300
4.2
RC2-310
4.2
RC2-320
4.2
RC2-340
4.2
RC2-370
4.2
RC2-410
4.0
RC2-470
4.8
RC2-510
5.3
RC2-550
6.1
RC2-580
5.3
RC2-610
6.1
RC2-620
6.1
RC2-710
7.4
RC2-790
7.4
RC2-830
7.4
RC2-930
7.4
RC2-1090
N/A
RC2-1280
N/A
RC2-1520
N/A
Chapter - 13. Pre-Start-Up Procedure
Summary of Contents for RC2 Series
Page 10: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 10 Figure 5 A Motor Wiring...
Page 16: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 16 Chapter 8 RC2 100 140 Installation Guide...
Page 17: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 17 Chapter 9 RC2 170 580 Installation Guide...
Page 18: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 18 Chapter 10 RC2 710 930 Installation Guide...