6.2.3. Boiler support
It is possible to mount the boiler on vibration dampers (available as option) to reduce noise transmission caused
by vibrations.
b
with vibration dampers
without vibration dampers
Melbury HE
530
580 630 700 800 895 1150 1300 1650 1900 2500 3000
Distance wall - boiler body front
D mm 1600 1700 1700 1900 1900 2000 2300 2300 2700 2800 3100 3300
Boiler length
T mm 1880 1995 1995 2215 2215 2320 2714 2714 3074 3284 3566 3851
Distance wall - boiler back
U mm 1000 1000 1000 1000 1000 1000 1000 1000 1000 1150 1150 1150
Distance wall - boiler flank *
V mm 600
600
600
600
600
600
600
600
600 1000 1000 1000
Boiler feet length
l mm 1580 1695 1695 1880 1880 1975 2314 2314 2674 2854 3096 3356
Boiler feet width
b mm 1000 1060 1060 1130 1130 1210 1300 1300 1375 1445 1570 1645
Measure
d mm
5
0
0
5
5
0
0
0
30
30
30
30
Silent block lenght
e mm
274
346
346
346
346
418
562
562
562
562
562
706
Silent block width
S mm
45
45
45
50
50
50
50
50
50
50
50
50
Number of silent blocks
4
4
4
4
4
4
4
4
4
6
6
6
U-girder width
S1 mm 50
50
50
55
55
55
55
55
55
55
55
55
Melbury C
530
580 630 700 800 895 1150 1300 1650 1900 2500 3000
Distance wall - boiler body front
D mm 1600 1700 1700 1900 1900 2000 2300 2300 2700 2800 3100 3300
Boiler length
T mm 2380 2495 2495 2755 2755 2925 3419 3419 3934 4214 4456 4716
Distance wall - boiler back
U mm 1000 1000 1000 1000 1000 1000 1000 1000 1000 1150 1150 1150
Distance wall - boiler flank *
V mm 600
600
600
600
600
600
600
600
600 1000 1000 1000
Boiler feet length
l mm 1580 1695 1695 1880 1880 1975 2314 2314 2674 2854 3096 3356
Boiler feet width
b mm 1000 1060 1060 1 130 1 130 1210 1300 1300 1375 1445 1570 1645
Measure
d mm
5
0
0
5
5
0
0
0
30
30
30
30
Silent block lenght
e mm
274
346
346
346
346
418
562
562
562
562
562
706
Silent block width
S mm
45
45
45
50
50
50
50
50
50
50
50
50
Number of silent blocks
4
4
4
4
4
4
4
4
4
6
6
6
U-girder width
S1 mm 50
50
50
55
55
55
55
55
55
55
55
55
* The dimension can be reduced to 200 mm, as long as this does not impair the operation of the control panel
and the ability to open a nearby furnace door.
The mounting instructions for the silent blocks can be found in the separate assembly guide.
Afterwards, you can start installing the connection tubes on the water and flue gas side.
Attention!
Once the boiler is filled up, it will come down by further 3-5 mm.