Melbury HE, C 530 - 3000
25
We reserve the right to make changes to dimensions and construction
edition 12.2020
Hamworthy Heating Limited – Dorset BH17 ONF
6.6. Boiler control panel and casing assembly
Please refer to the separate assembly guide enclosed with the supply.
The boiler casing should only be assembled after the boiler has been hydraulically connected otherwise, there is
a risk of damage of the casing. However, the casing must be mounted prior to connecting the unit to the flue!
6.7. Connecting the burner
6.7.1. Burner mating dimensions / orientation possibilities
Model
530 580-630 700-800 895 1150-1300 1650 1900 2500 3000
Furnace
Lenght
FRL mm 1517
1623
1794 188
9
2225 255
9
2745
2985
3265
Diameter
FR mm
516
549
614 640
675 71
2
750
811
870
Burner connection
Burner admittance diameter
M mm
230
3
0
0
330
3
8
0
Burner tube lenght min
max (qN max)
max (qN low NOx)
P mm
195
2
6
5
280
330
3
6
5
400
4
9
0
540
Screw hole centre diameter
Lk mm
330
400
4
5
0
4xM12,15° vers.
6xM12, 15° vers.
6xM16, 15° vers.
Maximum door load from burner
weight **
kg x m
140
160
180 200
220 25
0
280
320
360
Burner orientation
Max. swivel radius
R mm
720
760
835 880
940 100
0
1050
1145
1210
Distance boiler axle - pivot
D
1
mm
460
485
527 560
600 64
0
675
737
772
Distance door flange - pivot
D
2
mm
103
103
104 104
97
13
9
139
139
139
Door thickness
T mm
167
167
168 168
168 23
4
234
234
234
Door flange thickness
F mm
35
6
0
24.09.07
* Burner tube lengths without consideration of an eventual intermediate flange
** Load as burner weight x distance burner center of gravity - door. When necessary use a burner support.
Summary of Contents for Melbury C 1150