Melbury HE, C 530 - 3000
14
We reserve the right to make changes to dimensions and construction
edition 12.2020
Hamworthy Heating Limited – Dorset BH17 ONF
Technical specifications Melbury HE (natural gas)
Melbury HE
530 580 630 700 800 895 1150 1300 1650 1900 2500 3000
Power
Boiler nominal power qN (80/60°C)
max.
kW
530
580 630
700
800
895 1150 1300 1650 1900 2500 3000
min.
95
121 121
175
175
269
311
314 367
459
713 714
Calorific power qF
max.
kW
585
632 691
759
876
967 1248 1422 1815 2079 2725 3300
min.
3
99
127 127
182
182
280
324
327 383
478
743 744
Modulation rate
3
17% 20% 18% 24% 21% 29% 26% 23% 21% 23% 27% 23%
Efficiencies
Overall efficiency 60 / 80 °C
100%
%
90.7 91.8 91.3 92.2 91.4 92.5 92.2 91.4 90.9 91.4 91.7 90.9
Overall efficiency 60 / 80 °C
30%
%
95.2 95.5 95.4 95.7 95.6 95.9 95.8 95.7 95.5 95.7 96.0 95.6
Overall efficiency 60 / 80 °C
min qF
%
95.6 95.7 95.7 95.8 95.8 95.9 96.0 96.0 96.0 96.0 96.1 96.0
Efficiency DIN4702-8, 60 / 75 °C
η
N
%
94.6 95.0 94.9 95.2 95.0 95.4 95.3 95.1 94.9 95.1 95.4 95.0
Mass flows
Gas flow, NG type E
max.
1,2
nm
3
/h
58.7 63.4 69.3 76.2 87.9 97.0 125.2 142.7 182.1 208.6 273.4 331.1
min.
1,2
10.0 12.9 12.9 18.1 18.1 27.4 33.5 33.5 38.5 47.8 75.9 74.9
Exhaust gas mass flow
max. wet
kg/s 0.24 0.26 0.29 0.32 0.37 0.40 0.52 0.59 0.76 0.87 1.14 1.38
min. wet
0.04 0.05 0.05 0.08 0.08 0.11 0.14 0.14 0.16 0.20 0.32 0.31
Exhaust gas data, losses
Overpressure combustion chamber
max.
mbar 5.97 4.22 5.06 5.03 6.74 5.33 6.41 8.39 9.67 9.43 10.35 9.50
Exhaust gas temperature ati 80/60 °C
max.
°C
209
187 197
179
196
172
179
194 205
195
188 205
min.
3
95
Exhaust gas losses at 80/60 °C
max.
%
9.1
8.0
8.5
7.6
8.4
7.3
7.7
8.4
9.0
8.5
8.2
9.0
Stand-by loss qB
70 °C
W
781
883 883 1021 1021 1178 1382 1382 1565 1742 2073 2330
Hydraulic data
Water resistance
∆
t=10K
mbar
42
50
59
73
96
120
81
103 167
106
184
84
∆
t=20K
11
13
15
18
24
30
20
26
42
27
46
21
Water flow
max.
m3/h 30.4 33.2 36.1 40.1 45.8 51.3 65.9 74.5 94.5 108.8 143.2 171.8
Operating temperatures
max.
°C
95
SCO
110
Values acc. EN303-3 at:
3zugskessel, V-02/11
- lamda=1.15, CO2=10%
GG
- T-air=20°C, rel. humidity=60%, p-baro=100kPa
1: LCV = 9.97 kWh/nm3
2: nm3 at 0°C, 1013 mbar
3: S max = 10 mg / nm3
Flue gas temperature diagram Melbury HE, natural gas with clean boiler