Melbury HE, C 530 - 3000
21
We reserve the right to make changes to dimensions and construction
edition 12.2020
Hamworthy Heating Limited – Dorset BH17 ONF
6. Installation guide
6.1. Boiler room and boiler room ventilation
The boiler room must be arranged in compliance with local regulations and installation specifications. Particular
attention should be paid to the ventilation of the boiler room.
Supply of combustion air must be guaranteed (non-shut opening).
Minimum air requirement is 1.6 m
3
/h for each kW of boiler power.
Minimum free section of combustion air opening is 6 cm
2
for each kW of boiler power.
Important: The combustion air must not have high dust concentrations.
Furthermore, it must be free of halogens (chlorine and fluorine compounds). An excessive presence of
halogen in the combustion air leads to great corrosion damage. The maximum permitted amount of
halogen in the combustion air is 5 ppm.
Halogen compounds are found in spray cans, thinners, cleaning agents, degreasing agents and
solvents, among others. In addition, halogen emissions are strongly suspected in the vicinity of dry
cleaners', hair dressing salons, swimming pools, printing offices and washing machines installed in the
same room.
In the case of doubt, the perfect quality of the combustion air must be ensured with an external air
intake. Make sure that there is a minimum loss of pressure, since this could impair the performance of
the burner.
6.2. Planning dimensions
6.2.1. Space required
It must be possible to open the furnace door,
including burner, by 90°.
E = Burner length
A = E + d + 150 mm
When a sound proofing hood is used,
dimension D must be checked against the
dimensions of the hood (see chap. 4.4).
6.2.2. Boiler base
If the floor of the boiler room is moist or loose, a sufficiently high boiler base must be provided. Moisture does not
go well with electrical equipment!
A base is also a good idea if the height is not sufficient for installing the burner.
Otherwise, no base is needed for the Melbury HE series; the Melbury C series requires a base that is at least
100 mm high.