background image

0312734 / R4.0

ITS

Indirecte boiler
Dual coil indirect calorifier
Ballon double échangeur

Installatie-, Gebruikers- en Servicehandleiding
Installation, User and Service Manual
Manuel d'installation, d'utilisation et d'entretien

1019 / NL/EN/FR

ITS 400/500/600/750/1000

Summary of Contents for ITS Series

Page 1: ...iler Dual coil indirect calorifier Ballon double changeur Installatie Gebruikers en Servicehandleiding Installation User and Service Manual Manuel d installation d utilisation et d entretien 1019 NL E...

Page 2: ...sion A O Smith Water Heaters Unit B7 B8 Armstong Mall Southwood Business Park Farnborough Hampshire GU14 ONR UK A O Smith si ge France 14 all e Charles Path 18000 Bourges France T 0870 267 6484 sales...

Page 3: ...eiding bestaat uit 3 talen Handleiding ITS 400 t m 1000 5 Manual ITS 400 trough 1000 21 Notice ITS 400 1000 37 EN This manual consists of 3 languages Handleiding ITS 400 t m 1000 5 Manual ITS 400 trou...

Page 4: ...Installatie Service en Gebruikershandleiding 4...

Page 5: ...ucts Company is niet aansprakelijk voor claims van derden veroorzaakt door ondeskundig gebruik anders dan vermeld in deze handleiding en overeenkomstig de Algemene Voorwaarden gedeponeerd bij de Kamer...

Page 6: ...Installatie Service en Gebruikershandleiding 6...

Page 7: ...ling 9 Werkruimte 9 Verpakking 9 Afvoeren 9 Algemene gegevens 10 Afmetingen 10 Installatie 13 Aansluitschema 13 Wateraansluitingen 13 Vullen en Aftappen 15 Vullen 15 Aftappen 16 Onderhoud 17 Onderhoud...

Page 8: ...Installatie Service en Gebruikershandleiding 8...

Page 9: ...t afgeweken dan kan de bescherming van de tank niet worden gegarandeerd 4 Garantie In verband met de bereikbaarheid van het toestel wordt aanbevolen de volgende afstanden in acht te nemen bij de anode...

Page 10: ...31 1 33 1 86 1 93 1 7 Afmetingen Afmetingen Eenheid ITS 400 ITS 500 ITS 600 ITS 750 ITS 1000 A Totale hoogte mm 1710 2045 1840 2035 2005 D Diameter zonder isolatie mm 600 600 750 750 900 Diameter met...

Page 11: ...0312734_ITS_400 1000_NLENFR_V4 0 2019 03 08 11 Doorsnede vooraanzicht toestel IMD 1294 R0 0...

Page 12: ...Installatie Service en Gebruikershandleiding 12...

Page 13: ...isselaar G uitgang warmtewisselaar Installatie Schema IMD 0383 R2 0 2 2 Wateraansluitingen 2 2 1 Waarschuwing De installatie dient te geschieden door een erkend installateur en overeenkomstig de algem...

Page 14: ...eve van servicedoeleinden 4 Is een circulatieleiding nodig ga dan verder met het monteren van de circulatieleiding 2 2 3 Circulatieleiding Zo niet monteer dan de bij de aftapkraan geleverde afdichtmoe...

Page 15: ...an de circulatiepomp 6 2 Sluit aftapkraan 3 Open het dichtstbijzijnde tappunt 4 Open de toevoerkraan van de inlaatcombinatie 2 zodat koud water het toestel instroomt 5 Vul het toestel volledig Als uit...

Page 16: ...Gebruikershandleiding 16 3 2 Aftappen 1 Sluit de afsluiter in de warmwaterleiding 2 Sluit de toevoerkraan van de inlaatcombinatie 2 3 Open de aftapkraan 4 Belucht het toestel of installatie zodat het...

Page 17: ...eer de afvoerleidingen van de overstortventielen en verwijder aanwezige kalkresten 3 Tap het toestel af Het waterzijdig onderhoud bestaat uit het ontkalken en reinigen van de tank en het controleren v...

Page 18: ...nen de bouten aangedraaid te worden met een moment van maximaal 50 Nm Gebruik hiervoor geschikt gereedschap Controle anodes Anodes zorgen voor de bescherming van de tank door zich zelf op te offeren W...

Page 19: ...ievoorschriften van A O Smith geldend voor het specifieke model als de plaatselijk geldende installatie en bouwverordeningen voorschriften en regelingen van overheidswege b De boiler blijft ge nstalle...

Page 20: ...even garantie gaat niet verder dan kosteloze levering af magazijn van de te vervangen delen of onderdelen respectievelijk boiler vervoers arbeids installatie en andere met de vervanging verband houden...

Page 21: ...ised use use other than that stated in this manual and use other than in accordance with the General Conditions registered at the Chamber of Commerce Refer further to the General Conditions These are...

Page 22: ...Installation Service and User Manual 22...

Page 23: ...ing clearance 25 Packaging 25 Disposal 25 General specifications 25 Dimensions 26 Installation 29 Installation diagram 29 Water connections 29 Filling and Draining 31 Filling 31 Draining 32 Maintenanc...

Page 24: ...Installation Service and User Manual 24...

Page 25: ...e then the tank protection cannot be guaranteed 4 Warranty For access to the water heater it is recommended that the following clearances are observed around the anode connection 100 cm around the wat...

Page 26: ...ger top Capacity heat exchanger kW 37 42 40 56 58 Primary flow 80 60 C l h 1591 1806 1720 2408 2494 Pressure loss mbar 30 43 7 18 20 Heat exchange surface m2 1 15 1 31 1 33 1 86 1 93 1 7 Dimensions Di...

Page 27: ...ITS 1000 5 Connection circulation Rp Rp Rp Rp Rp 6 Diameter inspection opening mm 115 115 180 180 180 7 Connection T P Rp Rp Rp Rp Rp 8 Connection immersion well temp sen Rp Rp Rp Rp Rp 10 Connection...

Page 28: ...Installation Service and User Manual 28...

Page 29: ...points 15 expansion valve mandatory 16 expansion vessel mandatory A cold water supply B hot water supply C circulation pipe F inlet heat exchanger G outlet heat exchanger Installation Diagram IMD 0451...

Page 30: ...icing Circulation pipe See C in the installation diagram 2 1 Installation diagram If an immediate flow of hot water is required at draw off points a circulation pump can be installed This improves com...

Page 31: ...eater proceed as follows 1 Open the stop valve 11 in the hot water pipe and if present the stop valves 4 for the circulation pump 6 2 Close the drain valve 9 3 Open the nearest hot water draw off poin...

Page 32: ...vice and User Manual 32 3 2 Draining 1 Close the stop valve 4 between the cold water head tank and the cold water inlet A 2 Open the drain valve 9 3 Bleed the water heater or installation so that it d...

Page 33: ...scharge out 2 Check the drainage pipes from the discharge points of all valves and remove any scale deposits that may be present 3 Drain the water heater Water side maintenance consists of descaling a...

Page 34: ...d damage to the tank tighten the bolts that fasten the lid with a torque no greater than 50 Nm Use suitable tools for this Checking anodes Anodes ensure the protection of the tank by sacrificing thems...

Page 35: ...tructions for the specific model and the relevant government and local authority installation and building codes rules and regulations in force at the time of installation b The water heater remains i...

Page 36: ...O Smith pursuant to the specified warranty are limited to free delivery from the warehouse of the replacement assemblies parts or water heater respectively Shipping labour installation and any other...

Page 37: ...s r clamations de tiers li es une utilisation inad quate autre que celle mentionn e dans ce manuel d instructions et conform ment aux Conditions g n rales d pos es aupr s de la Chambre de commerce Voi...

Page 38: ...Notice d installation Mode d emploi Notice d entretien 38...

Page 39: ...de travail 41 Emballage 41 limination 41 Donn es g n rales 42 Dimensions 42 Installation 43 Sch ma de raccordement 43 Raccordement hydraulique 43 Remplissage Vidange 45 Remplissage 45 Vidange 46 Effe...

Page 40: ...Notice d installation Mode d emploi Notice d entretien 40...

Page 41: ...indiqu es dans le tableau la protection de la cuve ne pourra plus tre garantie 4 Garantie En ce qui concerne l accessibilit de l appareil il est recommand de tenir compte des distances minimales suiva...

Page 42: ...93 1 7 Dimensions Dimensions Unit ITS 400 ITS 500 ITS 600 ITS 750 ITS 1000 A Hauteur totale mm 1710 2045 1840 2035 2005 D Diam tre sans isolation mm 600 600 750 750 900 Diam tre avec isolation mm 740...

Page 43: ...NLENFR_V4 0 2019 03 08 43 Unit ITS 400 ITS 500 ITS 600 ITS 750 ITS 1000 8 Raccord immersion ainsi capteur de temp rature Rp Rp Rp Rp Rp 10 Raccord anode Rp 1 Rp 1 Rp 1 Rp 1 Rp 1 Vue de frontale des ap...

Page 44: ...Notice d installation Mode d emploi Notice d entretien 44...

Page 45: ...culation bouclage ECS F entr e changeur thermique G sortie changeur thermique Sch ma de raccordement IMD 0383 R2 0 2 2 Raccordement hydraulique 2 2 1 Avertissement L installation doit tre r alis e par...

Page 46: ...pour l entretien 4 Si une conduite de circulation est n cessaire continuez avec le montage d une conduite de circulation 2 2 3 Conduite de circulation Sinon montez alors l crou d tanch it avec le joi...

Page 47: ...dange 3 Ouvrez le point de puisage le plus proche 4 Ouvrez le robinet d arriv e du groupe de s curit 2 pour faire entrer de l eau froide dans l appareil 5 Remplissez l appareil enti rement L appareil...

Page 48: ...ntretien 48 3 2 Vidange 1 Fermez la vanne d arr t dans la conduite d eau chaude 2 Fermez le robinet d arriv e du groupe de s curit 2 3 Ouvrez le robinet de vidange 4 Purgez l appareil ou l installatio...

Page 49: ...2 V rifiez les conduites d vacuation des soupapes de trop plein er liminez les restes de calcaires pr sents 3 Vidangez l appareil L entretien du c t eau consiste d tartrer et nettoyer le r servoir et...

Page 50: ...iter tout dommage au r servoir les boulons doivent tre viss s avec un couple de 50 Nm maximum Utilisez cet effet l outillage adapt Contr le des anodes Les anodes assurent la protection du r servoir en...

Page 51: ...l compte tenu des prescriptions d installation appliqu es par A O Smith pour un mod le sp cifique et conform ment aux arr t s prescriptions et r glements officiels en ce qui concerne les installations...

Page 52: ...ns de A O Smith conformes la garantie accord e se limite la livraison gratuite de l entrep t des pi ces ou parties remplacer ou de l appareil remplacer Les frais de transport de travail d installation...