INSTALLATION REQUIREMENTS
3
The following limitations MUST be observed when siting the boiler:
a)
The boiler is not suitable for external installation. The position
selected for installation should be within the building, unless
otherwise protected by a suitable enclosure, and MUST allow
adequate space for installation, servicing, and operation of
the appliance, and for air circulation around it. (Section 2.3
and 3.4)
b)
This position MUST allow for a suitable flue system and
terminal position. (Section 2.6 and 3.3) The combination
boiler must be installed on a flat vertical wall which is capable
of supporting the weight of the appliance and any ancillary
equipment.
c)
If the combination boiler is to be fitted in a timber framed
building it should be fitted in accordance with the British Gas
publication ‘Guide for Gas Installations In Timber Frame
Housing’, Institute of Gas Engineers document IGE/UP-7. If in
doubt, advice must be sought from the Local Gas Supplier.
d)
If the appliance is to be installed in a room containing a bath
or a shower, any electrical switch or control utilising mains
electricity must be so situated that it cannot be touched by a
person using the bath or shower. Attention is drawn to the
requirements of the current l.E.E. Wiring Regulations
(BS7671), and in Scotland the electrical provisions of the
Building Regulations applicable in Scotland.
e)
A compartment used to enclose the appliance MUST be
designed and constructed specifically for this purpose. An
existing cupboard, or compartment, may be used provided it
is modified accordingly. BS 6798 gives details of the essential
features of cupboard / compartment design, including airing
cupboards.
f
) Where installation will be in an unusual location, special
procedures may be necessary. BS 6798 gives detailed
guidance on this aspect.
3.1
STATUTORY REQUIREMENTS
3.2
BOILER LOCATION
It is the law that all gas appliances are installed by a registered
person, in accordance with the rules in force. Failure to install
appliances correctly could lead to prosecution. It is in your own
interest, and that of safety, to ensure that the law is complied with.
In addition to the above regulations, this appliance must be
installed in accordance with the current IEE Wiring Regulations for
electrical installation, (BS 7671), local building regulations, the
Building Standards (Scotland) (Consolidation) Regulations, bye
laws of the local water undertaking and Health and Safety
Document No. 635 ‘The Electricity at Work Regulations 1989’.
It should also be in accordance with the relevant recommendations
in the current editions of the following British Standards and Codes
of Practice: BS5449, BS5546, BS5440-1:2000, BS5440-2:2000,
BS6798, BS6891, Institute of Gas Engineers document IGE/UP-7,
BS7074 (Expansion vessels)
.
IMPORTANT NOTE:
Manufacturer’s instructions must NOT be
taken in any way as overriding statutory obligations.
12
FLUE TERMINAL POSITION
Position Minimum
spacing
A
Directly below an openable window, 300mm 12in
air vent, or any other ventilation
opening
B
Below gutter, drain/soil pipe
75mm
3in
C
Below eaves
200mm
8in
D
Below a balcony
200mm
8in
E
From vertical drain pipes and
150mm
6in
soil pipes
F
From internal or external corners
300mm 12in
G
Above adjacent ground or
balcony level
300mm 12in
H
From a surface facing the terminal
600mm 24in
I
Facing terminals
1200mm 48in
J
From opening (door/window) in
1200mm 48in
carport into dwelling
K
Vertically from a terminal on the
1500mm 60in
same wall
L
Horizontally from a terminal on the
300mm 12in
same wall
M
Adjacent to opening
300mm 12in
N
Below carport
600mm 24in
O
From adjacent wall
300mm 12in
P
From adjacent opening window
1000mm 40in
Q
From another terminal
600mm 24in
R
Minimum height
300mm 12in
GAS SAFETY (INSTALLATION AND USE) REGULATIONS (CURRENT EDITION)
•
A
•
•
G
•
•
D,N
•
•
H,I
•
•
F
••
•
J
•
•
B,C
•
•
K
•
•
M
•
•
E
•
•
A
•
•
G
•
•
B,C
•
•
K
• •
F
•
•
F
•
•
C
•
•
K
•
•
K
•
•
G
• •
L
• •
L
•
•
P
•
•
300mm
MIN.
•
•
•
•
Q
•
•
R
•
O
430 mm
MIN.
•
•
O
SPECIAL REQUIREMENTS FOR A
VERTICALLY BALANCED FLUE
Summary of Contents for Ace High
Page 8: ...8 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended 8 6 00 6 ...
Page 25: ...INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM 23 ...
Page 26: ...7 2 ILLUSTRATED WIRING DIAGRAM 24 ...
Page 40: ...Ace Ace High Wickes Combi 82 102 05 04 ACE ACE HIGH WICKES COMBI 82 102 ...