Figure 41
Screen with channel in “Test”
Figure 42
Detector details screen in “Engineer“ level
TEST / EXIT TEST
This will put to TEST mode or take out of the TEST (EXIT TEST) mode the
selected channel. It is possible to put in TEST mode just parts of the system
when user level is “Maintenance” or “Engineer”. If more than half of the system is
selected, a warning screen will pop-up.
As far as the number of channels to put in Test/Maintenance mode does not
exceed the defined limits, the selected items will change the status into TEST, as
in the screen below:
The channels remain in TEST mode until the Channel Maintenance Time set
by the Configuration software (10-60 minutes) is expired. The EXIT TEST option
takes out of the Test/Maintenance mode the selected channel.
In the Channel list (figure above) screen, moving up and down with the
arrow keys through the Detectors list, choose 1 and press ENTER to get into
the detector’s details screen. This screen is the same for “Operator” and
“Maintenance” level, allowing only viewing the Detector configuration details.
Unlike the above, this screen seen as “Engineer” level, allows changing the
Detector’s details. See cofiguration software manual for more details.