Figure 38
Output details screen in “Engineer“ level
TEST / EXIT TEST
Will put to TEST mode or take out of the TEST (EXIT TEST) mode the select-
ed relay. It is possible to put in TEST mode just parts of the system at user level
“Maintenance” or “Engineer”. If more than half of the system selected, a warning
screen will pop-up.
Until the number of relays to put in Test/Maintenance mode does not exceed the
defined limits, the selected items will change the status into TEST.
The relay remains in TEST until the Channel Maintenance Time set for the con-
trol panel by the Configuration software (10-60 minutes) is expired.
The relays in TEST status can be activated and deactivated by the options 2-AC-
TIVATE and 4-DEACTIVATE.
The EXIT TEST option takes out of the Test/Maintenance mode the selected
relay. From the Relay list (Fig. 36), using the up/down arrow keys one may scroll
through the list choosing one of the relay and press ENTER to get into a sub-
menu. This screen is the same for “Operator” and “Maintenance” level, allowing
only to view the relay configuration details.
Unlike the above, this screen seen as “Engineer” level, allows changing the
relay’s timings. Refer to the separate cofiguration software manual for more
details.
Figure 39
Screen with the output operative details