SENSITRON
A Halma Company
MT2276E
GALILEO 32
Manual (EN)
P. 41/14
Warm Up Time
The warm-up time for the system after which it passes over to measuring mode
(from 2 to 10 minutes; default 3 minutes)
BUS Architecture
Which type of the BUS-architecture for the modules was implemented
by the installer:
2 Open Buss
4 Open Buss
Slave Address
Control panel address.
If the control panel is connected to a remote Scada system
Maintenance Time
Channel Test/Maintenance time after which a channel automatically switches
back to measuring mode (from 10 to 60 minutes; default 30 minutes)
Buzzer Reactivation Time
Reactivation time for buzzer after which the acoustic alarm is reactivated if the
alarm conditions are still valid (from 20 to 120 minutes; default 60 minutes)
In the “General Settings” it is indicated:
6.5.3
ZONES
Figure 6.5.3
Zones definition
screen
The creation of zones is not mandatory for the reliable function of the gas de-
tection system. It is an aid for the user to indicate useful additional information in
the case of alarms. The definition of “Zones” allows a logical dividing of the gas
detection system according the needs of the user. “Zones” may be defined in re-
lation to
-
the physical position of modules or detectors
-
measurement tasks like “LEL-monitoring” or “toxic” for workplace
safety
-
different gases like CH
4
or CO or O
2
A maximum number of 16 zones may be specified.
6.5.4
MODULES CONFIGURATION
IN/OUT modules and system detectors are set in “Input modules”. The system
layout must be known to correctly set the various field devices.
What you need to know:
-
Detectors and IN and OUT modules (relays) installed in the system.
-
The Zones they are in
-
The Buss (RS485 bus) they are connected to and their addresses
For information on Mult+S1 installation, please see chapter 2–Installing
in this manual.