SENSITRON
A Halma Company
MT2276E
GALILEO 32
Manual (EN)
P. 53/14
-
Add / Remove: To add or remove the events from the Associated
Sensors Modules window.
-
Programming of a new Relay Output: Selecting the new output, by
the Relay Type mode select if it is a Sensor event, a Module event or a
Generic event.
-
Sensor event: select Sensor in Relay Type. Then go to the Event Type
and select the type of the activation between: Underscale, Alarm1,
Alarm2, Alarm3, Overange, Overscale and Fault.
By pushing Add / Remove, the screen will allow you choose the channel address
or the input channels (to be associated to an output).
An open or closed lock on the left side is indicating the non latching or latching
status of the relay output.
After pushing the “Confirm” key, the output will be set with an event coming from
one or more sensors.
Figure 6.5.6
d) Sensor event
Figure 6.5.6
e) Channel choice screen