background image

DUAL DRYER SYSTEM
INSTALLATION/SERVICE
MANUAL (L31279)

®

Testing The GeminiMDx

 

Before placing the vehicle in service, perform the 
following tests:

1.  Close all reservoir drain cocks.

2.  Build up system air pressure to governor cut-out 
 

and note that the GeminiMDx dryer purges with an 

 

audible exhaust of air.

3.  Check for air leaks by applying a soapy water 
 

solution around the dryer manifolds, banjo bolts, 

 

pipe fittings, and dryer base.

4.  Actuate the service brakes to reduce system air 
 

pressure to governor “cut-in” pressure and ensure  

 

the compressor is in a loaded cycle. Note that the   

 

system once again builds to full pressure and is  

 

 

followed by a purge. 

5.   In order to check the Consep / ADV for proper  

 

 

operation the compressor must be in the 

 

compressor loaded cycle and the air governor must  

 

be between “cut-in” and “cut-out” pressure. This   

 

step can be performed concurrently with step 3. 

 

a.  Check the Consep for air leaks by applying a    

 

  soapy water solution around the manifolds,  

 

 

  banjo bolts, pipe fittings, and ADV mounting    

 

  area and drain port. 

 

b.  Observe the ADV for an audible click, either  

 

 

  during a brake application, timer function, or    

 

  multiplexing signal. As the ADV clicks, and          

 

  compressor loaded and governor between  

 

 

  “cut-in” and “cut-out”, the drain will expel a    

 

  small “puff” of air. If contaminants are present,  

 

  they will be expelled with the “puff”.

 

c.  Perform a manual drain test by depressing the 

 

  red button on the bottom of the valve. 

 

d.  To check the ADV valve’s heating element, turn  

 

  on the vehicle’s ignition. Wait ten minutes. The   

 

  valve should be warm to the touch. 

6.  Operational check of air dryer heater:
   a.  The heater can be checked while in the air
 

  dryer housing. 

 

b.  The air dryer temperature must be below 45°F    

 

  (thermostat closing temperature) to check the    

 

  heater resistance.  

 

c.  Set volt-ohmmeter to ohms.

 

d.  Disconnect the electrical plug.

 

e.  Connect the continuity tester to the heater

 

  element terminals.  

 6.  f.  Measure the resistance
 

    Acceptable 12VDC: 1.4-1.8 

W

 

    Acceptable 24VDC: 5.9-6.9 

W

 

g.  Replace heater if 12VDC is <1.4

 W

 

  or 24VDC is <5.9 

W. 

7.  It is recommended that the vehicle be tested for
 

leakage using the following procedure to assure

 

the GeminiMDx will not cycle excessively.

 

a.  Apply the parking brakes, build system pressure  

 

  to governor cut-out and allow pressure to

 

  stabilize for at least one minute.

 

b.  Observe the dash gauge pressures for two

 

  minutes and note any pressure drop. Pressure

 

  drop should not exceed 4 PSI with brakes

 

  released and 6 PSI with brakes applied. Any

 

  noticeable leakage must be repaired to avoid

 

  excessive dryer cycling.

9. 

Charge Cycle Time:

 During normal, daily

 

operation the compressor should recover from

 

governor cut-in to governor cut-out in 90 seconds

 

or less at engine RPM’s depending on vehicle

 vocation.

10. 

Purge Cycle Time:

 During normal, daily

 

operation the compressor must remain unloaded

 

for a minimum of 30 seconds between charge

 

cycles. This minimum purge time is required to

 

ensure complete regeneration of the desiccant. 

 

Operational Check

Page 12

Summary of Contents for GeminiMDx

Page 1: ...INSTALLATION SERVICE MANUAL High Capacity Dual Dryer System...

Page 2: ...nent until all recommended procedures have been read and are fully understood Use only the proper tools and observe all precautions pertaining to the use of those tools Components with stripped thread...

Page 3: ...stallation Instructions GeminiMDx 18 Cartridge Canister 18 Valve Unit with Integrated Purge Valve 19 12 24 VDC Heater Assembly 20 Outlet Check Valve Assembly 21 Turbo Protection Valve TPV 21 Cyclone I...

Page 4: ...rol purge manifolds banjo bolts sealing washers and one or two Consep units optional Dual Conseps 1 The two Conseps are identical They condense and separate contaminants from the compressed air The Au...

Page 5: ...directed upwards through the cyclone interior and out via the outlet port at the top of the housing Water and contaminants which have been condensed and separated flow downwards through a Filter 3 an...

Page 6: ...ns the Haldex patented MTC cartridge design which has five stages of drying The desiccant cartridge is contained by the canister and affixed to the dryer base with an o ring mounting collar and four b...

Page 7: ...der to stop the air compression and passes to the purge valve of each dryer via the control manifold The purge valve opens to atmosphere and depressurizes the air dryer The turbo protection valve TPV...

Page 8: ...Compressor Unloaded Time 30 seconds n a 30 seconds Maximum Duty Cycle 25 n a 25 Automatic Drain Valve 24VDC 1 0A 12VDC 2 0A 24VDC 1 0A 12VDC 2 0A n a Heater Element n a n a 24VDC 4 0A 12VDC 8 0A Heat...

Page 9: ...ANUAL L31279 Plumbing Schematics Page 7 Pre Treatment and Drying Drying Only WET TANK PURGE TANK GOVERNOR COMPRESSOR 1 4 18 NPTF 3 4 14 NPTF 3 4 14 NPTF WET TANK PURGE TANK GOVERNOR COMPRESSOR OPTIONA...

Page 10: ...DUAL DRYER SYSTEM INSTALLATION SERVICE MANUAL L31279 Page 8 Dimensions and Port Identification Dual Consep Assembly...

Page 11: ...DUAL DRYER SYSTEM INSTALLATION SERVICE MANUAL L31279 Dimensions and Port Identification Dual Dryer Assembly Page 9...

Page 12: ...DUAL DRYER SYSTEM INSTALLATION SERVICE MANUAL L31279 Dimensions and Port Identification Dual Consep Dual Dryer Assembly Page 10...

Page 13: ...ration Closes as temperature decreases to 45 7 F Opens as temperature increases to 71 6 F Normal Connect to 87 87A not used Heated Connect to 87A as shown 87 not used The heater terminals are non pola...

Page 14: ...tton on the bottom of the valve d To check the ADV valve s heating element turn on the vehicle s ignition Wait ten minutes The valve should be warm to the touch 6 Operational check of air dryer heater...

Page 15: ...t temperature can usually be accomplished with 12 to 15 of compressor discharge line Short life of air dryer or cartridge canister Air at inlet of dryer exceeds 170 F Extend length of compressor disch...

Page 16: ...n GeminiMDx purge tank and air tanks Monthly Operational check of all GeminiMDx functions Every Two Years Replace cartridge canisters Every Summer Ensure discharge line temperature is 170 F Every Wint...

Page 17: ...yer only DA37000 N4265AA Silencer 24 n a n a n a n a DQ6103 n a n a DA37100 N4265AB Tube 24 n a n a n a n a DQ6102 n a n a DA37005 N4265DA Silencer 24 n a n a n a n a DQ6103 n a n a DA37500 N4265EB Tu...

Page 18: ...DUAL DRYER SYSTEM INSTALLATION SERVICE MANUAL L31279 Page 16 Service Kit Components 34 36 33 28 2 1 3 7 9 10 11 12 13 19 14 15 16 17 18 8 4 5 6 32 23 31 22 30 21 20 24 29 25 26 27...

Page 19: ...LT 2 2 1 20 BOLT M22 BANJO LONG 4 21 WASHER M22 SEALING 8 8 8 8 8 8 8 8 8 8 8 22 MALE ELBOW 90 3 4 14 NPTF X 3 4 TUBE 1 23 MANIFOLD INLET OUTLET X 24 U BOLT NARROW X 25 NUT LOCKING M6 8 8 4 4 4 4 26A...

Page 20: ...rness 10 Reconnect air lines to the GeminiMDx manifolds and Consep inlet manifold Perform Operational Checks Page 12 NOTE Clean area above and around the GeminiMDx BEFORE removing the cartridge canist...

Page 21: ...oss pattern tighten the four mounting bolts to 32 35 ft lbs 43 47 Nm Valve Unit with Integrated Purge Valve NOTE Purge valve is not a serviceable item 1 Ensure air pressure is at 0 PSI in air system 2...

Page 22: ...silicone compound to green part of the seal Tighten M12 banjo bolt s to 130 150 in lbs 15 17 Nm 12 24 VDC Heater Assembly 1 Disconnect electrical plug from heating assembly 2 Remove the retaining scre...

Page 23: ...hten to 84 94 in lbs 9 5 10 5 Nm 8 Reinstall control manifold Apply a small amount of silicone grease to green part of banjo bolt seals Tighten M12 banjo bolts to 130 150 in lbs 15 17 Nm Turbo Protect...

Page 24: ...of banjo bolts seals Tighten banjo bolt s to M22 45 55 ft lbs 61 75 Nm M12 130 150 in lbs 15 17 Nm 10 Reconnect air line from system tanks to GeminiMDx 11 Reconnect air line from dryer manifold to Con...

Page 25: ...move all four mounting nuts 4 Remove cyclone and discard o rings OR If only replacing ADV for Consep clean cyclone and o rings 5 Apply grease to o rings Insert cyclone into Consep housing Align notch...

Page 26: ...ure loss Adsorption Process by which water and oil molecules at high pressure are captured by the desiccant Air Dryer A device that cools filters and dries the air delivered by an air compressor Compr...

Page 27: ...inside back cover blank...

Page 28: ...s trailers and buses We live and breathe our business delivering robust technically superior solutions born from deep insight into our customers reality By concentrating on our core competencies and f...

Reviews: