3-6
1.
Error
Messages
143
The device memory map number is not set in
the [Logging Server] window.
Check the device memory map settings, and set
correctly.
145
The device memory map number set in the
[Logging Server] window is not unique.
Check that the number is not duplicate in the
[Logging Server] window, and set correctly.
146*
Device memory map memory setting error
Contact your local distributor.
150
The ladder monitor program is not registered.
Transfer the ladder monitor program (.ldpA).
151
Ladder monitor program: Model setting error
Check the PLC model of the device connected,
and transfer the screen program again.
152
Ladder monitor program: Unsupported
language
Check the MONITOUCH model and the
language set in the screen program, and set
correctly.
155
FROM data unregistered
The “default.dtm” file has not been transferred
although the [Use Internal Flash ROM as
Back-up Area] checkbox is selected in the
[System Setting]
[Unit Setting]
[General
Settings] tab window.
As another possibility, no station number table is
found although [Yes] is selected for [Use Port
Number Table] under [Communication Setting]
in the [Hardware Setting] window.
When [Yes] is selected for [Use Port Number
Table], the capacity of Local mode extended
program becomes 66 KB smaller than the case
where it is not selected. Check the setting.
If the capacity is the same in either case,
contact your local distributor.
156
“Backup area” and “station number table”
cannot be used at the same time.
[Use Internal Flash ROM as Back-up Area] is
selected in the [System Setting]
[Unit Setting]
[General Settings] tab window although [Yes]
is selected for [Use Port Number Table] under
[Communication Setting] in the [Hardware
Setting] window.
It is not possible to use both functions at the
same time. Deselect either function, and
transfer the screen program again.
157
There are duplicated station numbers in the
station number table.
Be sure to set unique numbers when the station
number table is changed using the FROM_WR
macro command.
158
The model set for ladder monitor program is not
consistent with the one for ladder data.
Transfer the ladder data of the correct model.
159
PLC ladder data is incorrect.
Transfer the ladder data again.
160
The SRAM area size exceeds the available
range.
Check the settings in the [System Setting]
[Unit Setting]
[SRAM/Clock Setting] window.
161
The SRAM area is not formatted.
Format the SRAM area on the SRAM Setting
screen in Local mode.
Check that the battery voltage does not drop.
162
Data in the SRAM area does not match the
MONITOUCH system program version.
Check the MONITOUCH system program
version, and contact your local distributor.
163
The SRAM/clock setting does not match the
SRAM area format.
Format the SRAM area on the SRAM Setting
screen in Local mode.
164
The simulator program version does not match
the MONITOUCH system program version.
Check the MONITOUCH system program
version and the compatible simulator program
version.
165
Device memory map data is registered for a
model that does not support device memory
maps.
Delete the device memory map.
Error No.
Contents
Solution
Summary of Contents for Monitouch V9 Series
Page 1: ...Troubleshooting Maintenance Manual ...
Page 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Page 33: ...1 24 4 Status Bar Please use this page freely ...
Page 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Page 95: ...31 Error Messages 2 Troubleshooting Error Handling ...