164
SW03_3
~
SW03_8
Set the
communication
address with dip
switch
[3]
[4]
[5]
[6]
[7]
[8]
Communication address
ON OFF OFF ON OFF OFF
36#
ON OFF OFF ON OFF ON
37#
ON OFF OFF ON ON OFF
38#
ON OFF OFF ON ON ON
39#
ON OFF ON OFF OFF OFF
40#
ON OFF ON OFF OFF ON
41#
ON OFF ON OFF ON OFF
42#
ON OFF ON OFF ON ON
43#
ON OFF ON ON OFF OFF
44#
ON OFF ON ON OFF ON
45#
ON OFF ON ON ON OFF
46#
ON OFF ON ON ON ON
47#
ON ON OFF OFF OFF OFF
48#
ON ON OFF OFF OFF ON
49#
ON ON OFF OFF ON OFF
50#
ON ON OFF OFF ON ON
51#
ON ON OFF ON OFF OFF
52#
ON ON OFF ON OFF ON
53#
ON ON OFF ON ON OFF
54#
ON ON OFF ON ON ON
55#
ON ON ON OFF OFF OFF
56#
ON ON ON OFF OFF ON
57#
ON ON ON OFF ON OFF
58#
ON ON ON OFF ON ON
59#
ON ON ON ON OFF OFF
60#
ON ON ON ON OFF ON
61#
ON ON ON ON ON OFF
62#
ON ON ON ON ON ON
63#
Notes:
The communication address setting is written in the chip during energization of the valve box
1) Make sure that the communication address code is set before the valve box is energized.
2) Be sure to close the cover of the electrical cabinet after setting.
Summary of Contents for MRV 5-RC VP1-112B
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...