210
Failure code
Outdoor
digital
display tube:
114-4, 5
Indoor wired
controller:
72
Indoor unit LED status
LED5
Failure description:
Fan motor module DC BUS under voltage
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Failure diagnosis and troubleshooting
MRV 5-RC series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check the power supply
voltage is too low, resulting
in reduced voltage after
rectification;
◆
Check if the PTC is in
normal conditions;
◆
Check if the cabinet is
correctly wired.
3. Abnormity confirmation
conditions
When the power voltage
<DC283V, fault and alarm.
Voltage> DC283V, the
motor built-in control panel
automatically restored
4. Possible causes
◆
Incorrect wiring may result
in under voltage alarm;
◆
PTC or SCR damage may
result in under voltage;
◆
Low power voltage may
result in under voltage.
Check if the supply voltage is normal
and the cabinet is wired correctly.
Check if the PTC and SCR is
damaged.
When the fan running, testing the
DC voltage between DC + (red
line), DC- (white line) if it less
than 283?
Check the rectifier bridge,
reactor, electrolytic capacitor
of inverter main circuit
Replace the compressor module
Replace the fan motor
Adjust the supply voltage or
rewire the cabinet in accordance
with circuit diagram.
Y
Y
Y
N
N
N
Summary of Contents for MRV 5-RC VP1-112B
Page 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Page 3: ......
Page 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Page 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Page 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Page 116: ...113 2 Preparation before installation ...
Page 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Page 165: ...162 One by four valve box PCB code 0151800466 ...