Haier HSM-24HEA03-R2 Installation Manual Download Page 2

Indoor unit

Fix to side bar and lintel a mounting bar, Which is separately sold, and then

ƽ

fasten the plate to the fixed mounting bar.

Refer to the previous article, “ When the mounting plate is

ƽ

position of wall hole.

Make a hole of 70 mm in diameter, slightly descending to outside the wall.

ƽ

Install piping hole cover and seal it  off with putty  after installation

ƽ

When the mounting plate is first fixed

1. Carry out, based on the neighboring pillars or lintels, a 

to be fixed against the wall, then temporarily fasten the plate with one steel nail.

2. Make sure once more the proper level of the plate, by hanging a thread with a 

weight from the central top of the plate, then fasten securely the plate with the
attachment steel nail.

3. Find the wall hole location A using a measuring tape

When the mounting plate is fixed side bar and lintel

Fitting of the Mounting Plate and Positioning of the wall Hole

Lid for right
piping

Lid for under piping pipe

Fix with adhesive tape

Lid for left piping

Indoor/outdoor electric cable and drain hose must be bound with refrigerant

ƽ

piping by protecting tape.

[ Other direction piping ]

Cut away, with a nipper, the lid for piping according to the piping direction and

ƽ

then bend the pipe according to theposition  of  wall hole. When bending, be

careful not to crash pipes.

Connect beforehand the indoor/outdoor electric cable,

ƽ

and then pull out the

connected to the heat insulation of connecting part specially.

proper leveling for the plate

first fixed “, for the

Making a Hole on the Wall and Fitting the Piping Hole Cover

Drawing of pipe

Installation of the Indoor Unit

[ Rear piping ]

Draw pipes and the drain hose, then fasten them with the adhesive tape

ƽ

[ Left

Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.

ƽ

In case of left-rear piping, bend the pipes according to the piping direction to

ƽ

the mark  of  hole for left-rear piping which is marked on heat insulation materials.

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.

2. Insert the indoor/outdoor electric cable from backside of  indoor unit, and pull it

out on the front side, then connect them.

3. Coat the flaring seal face with refrigerant oil and connect pipes.

Cover the connection part with heat insulation materials closely, and make sure

fixing with adhesive tape

Fixing the indoor unit body

Hang surely the unit body onto the upper notches of the

ƽ

mounting plate. Move the body from side to side to verify its
secure fixing.

In order to fix the body onto the mounting plate,hold up

ƽ

the body aslant from the underside and then put it down
perpendicularly.

Connecting the indoor/outdoor Electric Cable

Removing the wiring cover

Remove terminal cover at right bottom corner of indoor unit, then take

ƽ

 off wiring cover by removing its screws.

1. Insert from outside the room cable into left side of the wall

hole, in which the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable

making a loop.

Note

When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not

be carried out and will cause defect.

Insert the cable from the back

ƽ

side of the unit, then pull it out on the front side.

Loosen the screws and insert

ƽ

the cable ends fully into terminal block, then

tighten the screws.

Pull the cable slightly to

ƽ

make sure the cables have been properly inserted and

tightened.

After the cable connection,

ƽ

never fail to fasten the connected cable with the

wiring cover.

mounting plate

When connecting the cable after installing the indoor unit

When connecting the cable before installing the indoor unit

When you unload the indoor unit,please use 

then lift the bottom of the body outward
slightly and lift the unit aslant until it
leaves the mounting plate. 

agraffe

mounting plate

Unloading of indoor unit body

ƽ

your hand to arise the body to leave agraffe,

Remote controller (1)

R-03 dry battery (2)

Mounting plate (1)

Drain hose (1)

Ø4X25 Screw (4)

Plastic cap (4)

Drain-elbow (1)

Cushion (4)

Pipe supporting plate (1)

Accessory parts

Liquid pipe (Ø)

6.35mm(1/4”)

Gas pipe (Ø)

mm(5/8”)

NOTE

˖

The thickness of the pipe must be 0.8mm at least.

Selection of pipe

2

15.88

A=150mm

B= 70mm

35mm

Heat insulation
material

Drain hose

Piping

Pipe supporting
plate

Indoor/outdoor electric cable

Indoor side

Outdoor side

Ø70mm

Wall hole

Thickness of wall

(Section of wall hole)

 Piping hole pipe

G

Summary of Contents for HSM-24HEA03-R2

Page 1: ...fail The power source is the same as the corresponding name plate Install an exclusive branch circuit of the power A receptacle shall be set up in a distance where the power cable can be reached Do not extend the cable by cutting it Power Source Preparation Please be subject to the actual product purchased the above picture is just for your reference Read this manual before installation Explain su...

Page 2: ... out on the front side then connect them 3 Coat the flaring seal face with refrigerant oil and connect pipes Cover the connection part with heat insulation materials closely and make sure fixing with adhesive tape Fixing the indoor unit body Hang surely the unit body onto the upper notches of the ƽ mounting plate Move the body from side to side to verify its secure fixing In order to fix the body onto...

Page 3: ...t perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Outdoor unit Indoor unit A B Outdoor unit Indoor unit A B A B Outdoor unit Indoor unit Oil trap Use the same method on indoor unit Loosen the screws on ƽ terminal block and insert the plugs fully into terminal block then tighten the screws Insert the cable according to terminal n...

Page 4: ... 1 5mm 1 5 2 0mm rth leakage breaker 4 Flare pipe Lean Damage of flare Crack Partial Too outside Correct Incorrect On Drainage It becomes high midway The gap with the ground is too small There is the bad smell from a ditch It waves The end is imm ersed in water Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below ƽ ƽ Please pour water in ...

Page 5: ...ar directa y suficientemente ventilado Elija un lugar que permita soportar el peso de la unidad y que no amplifique el ruido y las vibraciones Seleccione un lugar en el que los residuos y el viento generado por la unidad no cause una molestia a los vecinos Coloque la unidad en un lugar en el que pueda disponerse de la distancia de separación marcada X en la figura anterior Diagrama para la instala...

Page 6: ...r deben conectarse a la entubación del refrigerante utilizando cinta protectora Entubación en otra dirección Corte con una cuchilla la cubierta de entubación de acuerdo con la dirección de entubación y doble los tubos de acuerdo con la posición del orificio en la pares Tenga cuidado de no romper los tubos al doblarlos Conecte previamente el cable eléctrico de interior exterior y tire de la conexió...

Page 7: ...do con la unidad interior Afloje los tornillos del bloque de terminales e inserte los tapones completamente en los mismos Apriete entonces los tornillos Inserte el cable de acuerdo con el número del terminal de la misma forma que hizo con la unidad interior Si el cableado no es correcto no podrá alcanzarse la orientación correcta y el controlador podría resultar dañado Fije el cable con una pinza ...

Page 8: ...ro regulados por el Protocolo de Kyoto No los libere libremente a la atmósfera Tipo de refrigerante R410A Valor GWP 1975 GWP Potencial de contribución al calentamiento global Escriba con tinta indeleble 1 la carga de refrigerante que contiene el producto de fábrica 2 la cantidad de refrigerante adicional cargada durante la instalación y 1 2 la carga total de refrigerante en la etiqueta de carga de...

Page 9: ... luce diretta del sole e che sia sufficientemente ventilato Luogo in grado di sostenere il peso dell unità dove le vibrazioni ed il rumore non siano aumentati Luogo dove l aria di scarico ed il rumore non provocano disturbo ai vicini di casa Luogo dove sia disponibile una distanza contrassegnata da nella figura precedente Schema per l installazione dell unità interna ed esterna I modelli adottano ...

Page 10: ...o essere uniti alla tubatura refrigerante usando nastro protettivo Tubature con altre direzioni Tagliare con le tenaglie il coperchio per la tubazione in base alla direzione della stessa e piegarla in base alla posizione del foro sulla parete Quando si piega prestare attenzione e non spaccare i tubi Connettere prima il cavo elettrico interno esterno quindi estrarre la parte connessa all isolante t...

Page 11: ...ura Nota Solo per unità con pompa di calore fissarlo come in figura Nota Solo per unità con pompa di calore 1 Staccare il coperchio della porta di servizio della valvola a 3 vie il coperchio della valvola a stelo della valvola a 2 vie e della valvola a stelo della valvola a 3 vie collegare la porta di servizio nella protuberanza del tubo di carico basso del gruppo monometrico Poi collegare la prot...

Page 12: ...ttaccata accanto alla porta di caricamento del prodotto es all interno del coperchio con il valore di arresto A questo prodotto contiene gas serra fluorinato trattato nel Protocollo di Kyoto B carico di refrigerante del prodotto inserito in fabbrica vedere la piastra con il nome dell unità C quantitativo aggiuntivo di refrigerante caricato sul campo D carico di refrigerante totale E unità da ester...

Page 13: ...soit pas exposé à la pluie ou à la lumière du jour et qui soit suffisamment ventilé Sélectionnez un emplacement capable de supporter l unité où les vibrations et le bruit n augmentent pas Sélectionnez un emplacement où le vent et le bruit ne risquent pas de gêner les voisins Choisir un endroit dans lequel les distances marquées illustrées dans le schéma ci dessus sont disponibles Schéma de l insta...

Page 14: ...des matériaux d isolation thermique et fixez avec du ruban adhésif Le câble des unités intérieures extérieures et le tuyau de vidange doivent être fixé au tuyau de réfrigérant avec un ruban protecteur Tuyauterie dans une autre direction A l aide d une pince découpez le couvercle pour la tuyauterie en fonction de la direction de la tuyauterie et cintrez ensuite le tuyau selon la position du trou da...

Page 15: ...sérez totalement les fiches dans le bornier puis resserrez les vis Insérez le câble selon le numéro de la borne tel que pour l unité intérieure Si le câblage est incorrect le fonctionnement sera incorrect et le contrôleur risque de subir des dommages Fixez le câble avec un serre câble Fixation d un drain coudé Si vous utilisez un drain coudé procédez à la fixation selon l illustration Remarque uni...

Page 16: ...de réfrigérant R410A Valeur de GWP 1975 GWP global warming potential potentiel de réchauffement de la planète Merci de remplir à l encre indélébile 1 la charge de réfrigérant standard de l appareil 2 la quantité supplémentaire de réfrigérant chargée sur place et 1 2 la charge totale de réfrigérant sur l étiquette de charge de réfrigérant fournie avec l appareil L étiquette renseignée doit être col...

Reviews: