Recovery
means to
collect the refrigerant in a
special holding container.
Recycling
means to run the
refrigerant through
a filtering system to remove most particles and moisture.
Reclaiming
means to
chemically reprocess t
he refrigerant to return it to its original purity.
Recovering and recycling
refrigerant is possible with the aid of mechanical devices made for the
purpose .The recovery system is a compressor
/
pump assembly, which removes refrigerant from
a
system and safely stores it in a
D
epartment of Transportation (DOT) approved container until it is
re-used or returned for reclaim.
refrigerant may happen in the course of normal service.
When performing service on a refrigerant system, charging should be done using the best service
of refrigerant into the air. Proper charging of refrigerant system may require
removing some
refrigerant when the system is overcharged. and is to be used by personnel with
appropriate industry
experience recover the excess refrigerant.
Always use procedures so as not to release any refrigeran.
practices, ensuing that the least amount of refrigerant needed is used.
Lines must be evacuated before charging with refrigerant.
TEST EQUIPMENT
vacuum pump
Fig.10-1
equipment problem is sometimes caused by an improper installation. By completing this checklist the
conditioning system call for your records.
The following test equipment is recommended to properly service air conditioning equipment:
RECYCLINE DEVICE WHEN DOING REFRIGERANT SERVICE.
1. A good quality volt/ohm meter;
3. A Magnetic Gauge (capable of reading to 3” W.C.)
5. A clamp-on ammeter.
7. A micron meter (not shown)
9. Refrigerant recovery /recycling equipment
2. A two-channel temperature electronic thermometer;
4. A refrigerant pressure Gauge manifold set;
6. An electronic leak detector or bottle of soap suds.
8. A vacuum pump capable of pulling to 1000 microns;
Before beginning any troubleshooting procedure, complete the following installation checklist. An
problem may be found and corrected. Make copies of the checklist and complete one for every air
10.
1
INSTALLATION AND SERVICE CHECKLIST
(Refer to the unit installation instructions for the specifics)
ELECTRICAL
………….Proper equipment ground to the electrical panel
………….Correct the thermostat and subbase
The authors of the EPA regulations enforcing the Clean Air Act realized that an accidental release of the
WARNING : IN ORDER TO COMPLAY WITH FEDERAL LAW, ALWAYS USE A RECOVERY /
………….Correct line voltage supplied to indoor and outdoor units
………….Proper disconnect switches and breakers for indoor and outdoor units
………….Correct control voltage at outdoor unit and transformer adequate for all control voltage loads
………….Correct wire size for both indoor and outdoor units.
24
Central Air Conditi
oning
Model: Heat Pump,
HR13-D2