Service diagnosis
42 Domestic air conditioner
10.3.9 Overheat Protection For Discharge Temperature
Outdoor display:
ƵƾƵ
F4 LED1 flash 8 times
Method of The Discharge temperature control is checked with the temperature being detected
Malfunction by the Discharge pipe thermistor
Detection
Malfunction when the compressor discharge temperature is above 110
ć
Decision
Conditions
Supposed
Ŷ
Electronic expansion valve defective
Causes
Ŷ
Faulty thermistor
Ŷ
Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the remote controller,
then measure the temperature at the exhaust temperature sensor of
the compressor on the outdoor unit
The temperature exceeds
110
ć
shortly after the
machine starts up?
1) The cryogen may have been leaked during
installation, or there may be leakage in the piping
system.
2) There may be other causes to make the exhaust
temperature too high.
Malfunctions occur after running for some time even
though the measured temperature is below 110
ć
. Pull
out the exhaust sensor and measure its resistance at
standard temperatures according to the
resistance-temperature table
The results deviate
much?
The sensor is damaged. Replace the sensor
with a new one.
The outdoor mainboard is damaged and needs be
replaced
YES
NO
NO
YES
Summary of Contents for 1U68REMFRA
Page 11: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40 ...
Page 39: ...Service diagnosis 37 Domestic air conditioner ...
Page 46: ...Service diagnosis 44 Domestic air conditioner ...
Page 58: ...58 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram ...
Page 59: ...57 Do C omestic air ircuit Diagra conditioner ams r ...