Functions and control
19 Domestic air conditioner
(18K/24K)
TC(
ć
) The compressor stops Fgh_t1 63
ć
/63
ć
Fgh_t1
ˉ
2
Fgh_t2
ˉ
2 N Decreasing the frequency rapidly Fgh_t2 59
ć
/59
ć
P Decreasing the frequency slowly Fgh_t3 56
ć
/57
ć
Fgh_t3
ˉ
2
Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 53
ć
/51
ć
R Increasing slowly Fgh_t5 40
ć
/40
ć
Fgh_t5—2
Normal
N
˖
Decreasing at the speed of 1HZ/1 second
P
˖
Decreasing at the speed of 1Hz/10 seconds
Q
˖
Continue to keep the last-time instruction cycle
R
˖
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
ƽ
During the starting process of the compressor, if the current of the compressor is greater than 15.5A
/17A(18K/24K)for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such
state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Then continue to run it only after the power is off.
ƽ
During the starting process of the compressor, if the AC current is greater than 14.5A/15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 13.5A/14A(18K/24K),
the frequency of the compressor decreases at the speed of 0.1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 13A/13A(18K/24K),
the frequency of the compressor increases at the prohibited speed.
ƽ
During the starting process of the compressor, if the AC current is greater than 11.5A/12A(18K/24K)
the frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 15.5A/17.5A(18K/24K)
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
During the starting process of the compressor, if the AC current is greater than 14.5A 15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
Summary of Contents for 1U68REMFRA
Page 11: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40 ...
Page 39: ...Service diagnosis 37 Domestic air conditioner ...
Page 46: ...Service diagnosis 44 Domestic air conditioner ...
Page 58: ...58 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram ...
Page 59: ...57 Do C omestic air ircuit Diagra conditioner ams r ...