Service diagnosis
35 Domestic air conditioner
10.3.3 Indoor AC fan motor malfunction
Indoor Display
Ƶƶƾ
E14
Method of The rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction abnormal fan motor operation
Detection
Malfunction when the detected rotation feedback signal don’t received in 2 minutes
Decision
Conditions
Supposed
Ŷ
Operation halt due to breaking of wire inside the fan motor.
Causes
Ŷ
Fan motor overheat protection
Ŷ
Operation halt due to breaking of the fan motor lead wires
Ŷ
Detection error due to faulty indoor unit PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Check whether terminals
on indoor pcb is well ?
Electrify the machine again and turn it on in the cooling operation,
Measure voltage between the positions 1and 3 of Terminal CN5
on the indoor PCB
the voltage is about 90-220vac
check whether motor can run
when turn on the unit
the indoor motor is damaged and need replace
Yes
12
12
<HV
Measure whether there is voltage pulse (0-5VDC)
between the positions middle wire and black wire
of Terminal CN2 on the indoor PCB
12
the indoor pcb is damaged and need replace
Pull out the terminals on the indoor
mainboard and reinsert them.
1R
<HV
Is it ok?
<HV
Summary of Contents for 1U68REMFRA
Page 11: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40 ...
Page 39: ...Service diagnosis 37 Domestic air conditioner ...
Page 46: ...Service diagnosis 44 Domestic air conditioner ...
Page 58: ...58 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram ...
Page 59: ...57 Do C omestic air ircuit Diagra conditioner ams r ...