Installation, handling and maintenance
74
Technical changes reserved
7.3.4
Assembly principle for connection joints with protection type
IP68
Step
Action
1
Remove the two transport protection steel plates at the end of the
busbar elements (on the non-jointed side) and dispose of them.
2
Remove the 4 covers for the joint block (flanges of the joint block).
3
Before connecting, make sure that the ends of the busbar elements and
the joint block are clean and undamaged.
4
Insert the ends of the busbar elements carefully into the joint block.
5
Push the two elements together so that the distance is 220 mm. Take
care that the inner conductors in the joint block are all aligned evenly.
6
Tighten the shear-off bolt on the single bolt clamp until the
double-headed bolt shears off. This occurs at approximately 60 Nm.
7
Check the insulation resistance. It will not be possible to perform this
check after filling with the casting resin mixture.
8
Fit the side flanges.
Summary of Contents for KEH31D00S3LMA
Page 1: ...Busbar system unibar H System manual 800 A to 4000 A...
Page 10: ...Construction and characteristics 10 Technical changes reserved...
Page 19: ...Construction and characteristics Technical changes reserved 19 Notices...
Page 40: ...Product selection 40 Technical changes reserved Copper...