Installation, handling and maintenance
72
Technical changes reserved
7.3.3
Assembly principle for connection joints with protection type
IP55/IP65
Step
Action
1
Remove the two transport protection steel plates at the end of the
busbar / busbar element (on the non-jointed side) and dispose of them.
2
Remove the 4 covers for the joint block (flanges of the joint block).
3
Before connecting, make sure that the ends of the busbar elements and
the joint block are clean and undamaged.
4
Insert the ends of the busbar elements carefully into the joint block.
5
Push the two busbar elements together so that the distance is 220 mm.
Take care that the inner conductors in the joint block are all aligned
evenly.
6
Tighten the shear-off bolt on the single bolt clamp(s) until the
double-headed bolt shears off. This occurs at approximately 60 Nm.
7
Fit the side flanges.