HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

6. Seal around the edge.

 

Seal around the edge of the damper with a fire-resistant 
sealant.

7. Fix the duct  

Fix the duct to the damper fitting with screws.  

Check that the screws do not hinder damper blade  
movement.

8. Protection grilles 

If the fire/fire gas damper is not connected to the duct 
system, e.g. when installing as a closing device or transfer air 
device, the damper must be fitted with protection grilles on 
the non-connected side. The minimum permissible distance 
between the damper blade in the open position and the 
grille is 50 mm. Install the thermal sensor.  

Check that the screws and the thermal sensor do not 
hinder damper blade movement.

Ø9mm

50 mm

If the fire/fire gas damper is not connected to the duct 
system, go to step 8.

The installation must be equal to the building component’s fire 
resistance class.

Drawing name:

Summary of Contents for INTACT

Page 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Page 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Page 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Page 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Page 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Page 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Page 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Page 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Page 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Page 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...

Reviews: