HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

There is a handle on the engines for dimension 100-315 
mm. The handle shall be in position 1, with exception for 
when the control require position 2.

1. (0)2-10 VDC
2. 2-10 VDC
3. Do not use, hinders rotation of the blade
4. Do not use, hinders rotation of the blade

CONTROL

The fire gas damper must be function tested at least once 
every 48 hours. The function test means that the dampers 
must close and open at intervals as above. 

The function test must be performed automatically and can  
be controlled by e.g. a control and monitoring system. 

05  2022

Hagab

  Box 135, 562 02 Taberg  

|

  

Visit

 Industrivägen 5, 562 41 Taberg  

|

  

Phone

 036-36 30 90  

|

  Fax

 036-36 30 99

[email protected]  

|

  www.hagab.com  

|

  

Sales Office

 

Jönköping 

Phone

 036-36 30 90  

|

  Stockholm 

Phone

 08-689 90 10

2

1

L1

N

M

S2

S1

<5˚

<80˚

S5

S4

S6

S3

-

+

~

AC 24 V

DC 24 V

AC 230 V

2

1

S2

S1

<5˚

<80˚

S5

S4

S6

S3

3

4

U

Y

-

+

~

DC (0)2...10 V

DC 2...10 V

TF1 TF2

LED

Test

OPERATING AND MAINTENANCE  

INSTRUCTIONS

Periodic inspection once per year.

INTERNAL CONTROL VIA INSPECTION COVER 
OR CLEANING HATCH IN CONNECTING DUCT

– Check by triggering the smoke detector so the  damper  
 closes.

– Check that the damper blade closes and opens freely by  
  switching off power to the actuator. If the junction box  
  KBHA-1 is installed, press the “DAMPER TEST” button. 
  Keep the button pressed to interrupt the voltage to the  
  actuator. Alternatively, the voltage can be interrupted by  
  pressing the “Test” button on the damper’s thermal sensor.

– Check the fitting of the sealing strip on the damper blade.

– Check the cleaning requirements in conjunction with the  
  ventilation system function test.

EXTERNAL CONTROL

– Check that the damper frame has not been  
  subjected to mechanical damage.

– Check that the seal in the structural element has 
  not been damaged.

– Check the fitting of the actuator on the shaft and frame.

– Check that the actuator cabling is not damaged.

– Check that the damper is clean. If necessary, wipe with  
  a slightly dampened cloth.

CLEANING 

– When cleaning the inside of the damper, always choose  
  a gentle cleaning method such as a nylon brush and/or  
  compressed air.

SPARE PARTS LIST

 

See rating plate on the actuator.

WIRING DIAGRAM

1

4

3

2

HANDLE

WIRING DIAGRAM (ADJUSTABLE)

Drawing name:

Summary of Contents for INTACT

Page 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Page 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Page 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Page 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Page 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Page 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Page 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Page 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Page 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Page 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...