HAGAB – INSTALLATION, OPERATION AND MAINTENANCE
INTACT
Fire/Fire gas damper
EASIER INSTALLATION
NEW
1.
INSTALLATION OF DAMPERS
AGAINST STRUCTURAL ELEMENTS
WITHOUT CAULKING AND REFINISHING
1. Hole dimensions
Damper dim5 mm for sizes 100-315 mm.
Damper dim10 mm for sizes 400-630 mm
4. Sealing
Seal between the damper and the wall with a fire-resistant
sealant.
2. Angle brackets
Fix the supplied angle brackets spaced evenly
around the damper.
Angle bracket
(supplied)
3. Fix the duct
Fix the duct to be installed through the structural element
against the damper fitting with flat head screws. Check that
the screws do not hinder damper blade movement.
Note the installation direction of the damper.
5. Centre in the hole
Place the damper casing flush against the structural element,
centre it in the hole and fix with the angle brackets.