HAGAB – INSTALLATION, OPERATION AND MAINTENANCE
INTACT
Fire/Fire gas damper
4. Thermal sensor
Install the thermal sensor with the sensing unit in the air flow without hindering damper blade movement.
5. Insulation
Insulate the duct to an approved method according to the insulation supplier’s instructions.
Note that the insulation must cover the whole damper.
6. No connection in the duct system
If the damper is not connected to the duct system, e.g. when installing as a closing device or transfer air device, the damper must be
fitted with protection grilles on the non-connected side. The minimum permissible distance between the damper blade in the open
position and the grille is 50 mm.