background image

4

HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

2. INSTALLATION OF DAMPERS  
WITH AN INSTALLATION SLEEVE 

WITH CAULKING AND REFINISHING

1.

 

Hole dimensions 

 

Damper dim50 mm.

2. Installation sleeve

  

For installation in light stud walls, use an installation sleeve. Fit 
the installation sleeves together from each direction against 
the wall/structural element and screw them together. 

4. Centre in the hole

 

Place the damper casing flush against the structural element, 
centre it in the hole and fix laterally with the damper and 
duct system suspension devices.

3. Fix the duct

 

Fix the duct to be installed through the structural element 
against the damper fitting with plate screws.  

Check that the screws do not hinder damper blade 
movement.

 

Note the installation direction of the damper.

5. Lead-though/Sealant 

The space between the installation 
sleeve and connecting duct can 
be fitted with fireproof insulation 
made of mineral wool or an  
equivalent sealant. Seal after  
with a fire-resistant sealant.

Drawing name:

Summary of Contents for INTACT

Page 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Page 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Page 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Page 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Page 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Page 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Page 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Page 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Page 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Page 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...

Reviews: