Summary of Contents for FD-3V

Page 1: ......

Page 2: ... Fusible Link Operating Temperature Max Pressure A 0 5 kPa 2 in w g A 74 165 Closure Operating B 1 0 kPa 4 in w g B 100 212 Closure Operating C 1 5 kPa 6 in w g C 121 250 Operating D 2 0 kPa 8 in w g D 141 286 Closure Operating E 2 5 kPa 10 in w g E 177 350 Closure Operating UL Classified UL 555 Listing R26192 See Complete Marking on Product The FD 3V damper meets the following requirement for fir...

Page 3: ...Fusible Link Temperature 165 74 is Standard Minimum Size 4 x 4 102mm x 102mm Maximum Size Single Section 36 x 36 914mm x 914mm Multiple Section 108 x 72 2743mm x 1829mm OPTIONS Factory installed sleeve Gauge 19 1 2mm 16 1 6mm Length 12 305mm 16 406mm Other Factory installed Standard Flange Double Flange Sleeve Alternate fire closure temperature 212 100 286 141 350 177 ...

Page 4: ... B 1 0 kPa 4 in w g 2 1 5hr C 1 5 kPa 6 in w g 3 3 0hr F Temperature C Mounting A 74 165 Operating V Vertical B 100 212 Operating H Horizontal C 121 250 Operating D Max Velocity D 141 285 Operating 1 10 2 m s 2000 fpm E 177 350 Operating UL Classified UL 555 Listing R26192 See Complete Marking on Product The FDB 3V damper meets the following requirement for fire dampers established by National Fir...

Page 5: ... in frame Springs Stainless Steel Bearings Stainless steel oilite sleeve type Fusible Link Temperature 165 74 is Standard Minimum Size 12 x 8 305mm x 203mm Maximum Size Single Section 36 x 36 914mm x 914mm Multiple Section 108 x 72 2743mm x 1829mm Component ITEM NAME 1 Top Down Frame 2 Side Frame 3 Concealed Linkage 4 Bearing 5 Jamb Seal 6 Blade 7 Clip Shaft Base 8 Jackshaft 9 Joint 10 Spring 11 F...

Page 6: ...ory installed No Sleeve Standard Sleeve Factory installed sleeve Gauge 19 1 2mm 16 1 6mm Length 12 305mm 16 406mm Other Alternate fire closure temperature 212 100 286 141 350 177 Sleeve optional No Sleeve Standard ...

Page 7: ... may cause product damage personal injury and other circumstances Before the installation use and maintenance please read the installation manual and maintenance manual first The installation manual is for the user only after the damper installation is complete please give the final user of this manual WARRANTY The Flowtech provide the products for one year warranty Under the warranty period the d...

Page 8: ...0285 6 E mail ydc28066 ms8 hinet net flow tech msa hinet net Laboratory No 102 Neihu 1st Rd Dongshan Township Yilan County Taiwan 269 Tel 886 3 961 0891 Fax 886 3 961 0897 Factory No 658 Meilin Rd De an Village Dongshan Shiang Yilan County 269 Taiwan R O C Tel 886 3 9612 449 Fax 886 3 9615 843 CNo CAT FD FDB December 2014 ...