2-3
Table2-1 Temperature requirements
Temperature
Range
Operating temperature
0°C to 40°C (32°F to 104°F)
Storage temperature
–40°C to +70°C (–40°F to +158°F)
Humidity
Maintain appropriate humidity in your equipment room, as described in
•
Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical
property change of materials, and metal corrosion.
•
Lasting low relative humidity can cause washer contraction and ESD and cause problems
including loose mounting screws and circuit failure.
Table2-2 Humidity requirements
Humidity
Range
Operating humidity
5% to 95%, noncondensing
Storage humidity
5% to 95%, noncondensing
Cleanliness
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points. In the worst case, electrostatic adsorption can cause
communication failure.
Table2-1 Dust concentration limits in the equipment room
Substance
Particle diameter
Concentration limit
Dust particles
≥ 0.5 µm
≤ 3.5 × 10
6
particles/m
3
Dust particles
≥ 5 µm
≤ 3 × 10
4
particles/m
3
Dust (suspension)
≤ 75 µm
≤ 0.2 mg/m
3
Dust (sedimentation)
75 µm to 150 µm
≤ 1.5 mg/(m
2
h)
Corrosive gases can accelerate corrosion and aging of components. Make sure the corrosive gases
in the equipment room do not exceed the concentration limits as shown in
Table2-2 Corrosive gas concentration limits in the equipment room
Gas
Average concentration (mg/m
3
)
Maximum concentration (mg/m
3
)
SO
2
0.3
1.0
H
2
S
0.1
0.5
Cl
2
0.1
0.3
HCI
0.1
0.5
HF
0.01
0.03
NH
3
1.0
3.0
Summary of Contents for S12500G-AF Series
Page 32: ...3 15 Figure3 16 Connecting the grounding cable to a grounding strip 1 2 4 3 6 5 ...
Page 49: ...4 16 Figure4 16 Connecting an SFP DAC cable 1 Pull latch 2 Connector 1 2 ...
Page 92: ...A 12 FigureA 14 Example of a device label ...
Page 104: ...C 6 FigureC 5 Securing the chassis to the pallet base S12504G AF switch 1 1 2 2 1 ...