OPERATION
67
Parallel Output
Connection
-
+
Load
Master
unit
Slave
unit 2
Slave
unit 1
Steps
1.
Ensure the power is off on all power supplies.
2.
Choose a master and a slave unit(s).
3.
Connect the analog connectors for the master
and slave unit as shown above.
4.
Remove the Output Terminal
covers and the protection dummy
plug from the analog control
connector.
Page 42
5.
Connect the master and slave unit in parallel as
shown above.
6.
Reattach the terminal covers.
Page 42
Note
Ensure the load cables have sufficient
current capacity.
Page 39
Re-attach the Protection dummy plug when not in
use.