45
Expert Power Control 8221/8226
© 2022 GUDE Systems GmbH
Configuration
The switching function can be set in more detail on the "Action PortSwitch" register.
Port 1 is switched on. You could extend the rule and switch more ports on or off. Addi-
tionally you can set a time for a batchmode in the field after "Between Action1 and Ac-
tion 2 : wait", which starts "Action 2" after expired time. However, the batch mode has
the disadvantage that it is not automatically restarted when the device is rebooted. Also,
the port is locked against manual operation on the web page as long as the batch mode
is running.
The "Action PortSwitch" function is only available for devices with switchable ports.
Extending a rule
For demonstration purposes, here is an extension to the simple timer from the previous
example:
The action is now started not only at 9:30, but also at 17:30 There are other changes:
The timer is only active between October and December, also the action does not take
place on the first day of a month.
Since all fields in the mask are always considered, it is not possible to define the
times 9:30 and 17:10 in a single timer rule. You need a second rule for this. If you set
the hours 9 and 17, as well as the minutes 10 and 30, then the four times 9:10, 9:30,
Summary of Contents for Expert Power Control 8221 Series
Page 2: ...2 Expert Power Control 8221 8226 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 14: ...Operating ...
Page 25: ...Configuration ...
Page 54: ...Specifications ...
Page 109: ...Support ...