11
Expert Power Control 8221/8226
© 2022 GUDE Systems GmbH
Device Description
1.7.1
Electrical Measurement
typical fault tolerances for Ta=25°C, I=1Arms...16Arms, Un=90Vrms...265Vrms
Electrical Measurement Specification
Category
Range
Unit
Resolu-
tion
Inaccuracy
(typical)
Voltage
90-265
V
0.01
< 1%
Current
0 - 16
A
0.001
< 1.5%
Frequency
45-65
Hz
0.01
< 0.03%
Phase
-180 - +180
°
0.1
< 1%
Active power
0 - 4000
W
1
< 1.5%
Reactive power
0 - 4000
Var
1
< 1.5%
Apparent power 0 - 4000
VA
1
< 1.5%
Power factor
0 - 1
-
0.01
< 3%
Energy Counter
Active Energy
(total)
9.999.999,999
kWh
0.001
< 1.5%
Active Energy
(resettable)
9.999.999,999
kWh
0.001
< 1.5%
1.8
Sensor
Two external sensors can be connected to the
Expert Power Control 8221-1/8226-1
.
The following sensors are currently available