52
Expert PDU Energy 8311
© 2021 GUDE Systems GmbH
Specifications
Index of Power Channel entries
pdu8311ChanStatus
.62.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
pdu8311AbsEnergyActive
.62.1.5.1.2.1.3.x
Unsigned32
RO
Absolute Active Energy counter.
pdu8311PowerActive
.62.1.5.1.2.1.4.x
Integer32
RO
Active Power
pdu8311Current
.62.1.5.1.2.1.5.x
Unsigned32
RO
Actual Current on Power Channel.
pdu8311Voltage
.62.1.5.1.2.1.6.x
Unsigned32
RO
Actual Voltage on Power Channel
pdu8311Frequency
.62.1.5.1.2.1.7.x
Unsigned32
RO
Frequency of Power Channel
pdu8311PowerFactor
.62.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
pdu8311Pangle
.62.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
pdu8311PowerApparent
.62.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
pdu8311PowerReactive
.62.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
pdu8311AbsEnergyReactive
.62.1.5.1.2.1.12.x
Unsigned32
RO
Absolute Reactive Energy counter.
pdu8311AbsEnergyActiveResettab
le
.62.1.5.1.2.1.13.x
Unsigned32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all
resettable counter.
pdu8311AbsEnergyReactiveResett
able
.62.1.5.1.2.1.14.x
Unsigned32
RO
Resettable Absolute Reactive Energy counter.
pdu8311ResetTime
.62.1.5.1.2.1.15.x
Unsigned32
RO
Time in seconds since last Energy Counter reset.
pdu8311ForwEnergyActive
.62.1.5.1.2.1.16.x
Unsigned32
RO
Forward Active Energy counter.
pdu8311ForwEnergyReactive
.62.1.5.1.2.1.17.x
Unsigned32
RO
Forward Reactive Energy counter.
pdu8311ForwEnergyActiveResetta
ble
.62.1.5.1.2.1.18.x
Unsigned32
RO
Resettable Forward Active Energy counter.
pdu8311ForwEnergyReactiveRese
ttable
.62.1.5.1.2.1.19.x
Unsigned32
RO
Resettable Forward Reactive Energy counter.
pdu8311RevEnergyActive
.62.1.5.1.2.1.20.x
Unsigned32
RO
Reverse Active Energy counter.
pdu8311RevEnergyReactive
.62.1.5.1.2.1.21.x
Unsigned32
RO
Reverse Reactive Energy counter.
pdu8311RevEnergyActiveResettab
le
.62.1.5.1.2.1.22.x
Unsigned32
RO
Resettable Reverse Active Energy counter.
pdu8311RevEnergyReactiveResett
able
.62.1.5.1.2.1.23.x
Unsigned32
RO
Resettable Reverse Reactive Energy counter.
pdu8311ResidualCurrent
.62.1.5.1.2.1.24.x
Unsigned32
RO
Actual Residual Current on Power Channel. According Typ A IEC
60755. Only visible on models that support this feature.
pdu8311LineSensorName
.62.1.5.1.2.1.100.x
OCTETS
RW
A textual string containing name of a Line Sensor
epc8311NTPTimeValid
.62.1.5.15.1.0
INTEGER
RO
Show if valid Time is received
epc8311NTPUnixTime
.62.1.5.15.2.0
Unsigned32
RO
show received NTP time as unixtime (secs since 1 January 1970)
epc8311NTPLastValidTimestamp
.62.1.5.15.3.0
Unsigned32
RO
show seconds since last valid NTP timestamp received
pdu8311SensorIndex
.62.1.6.1.1.1.x
Integer32
RO
None
pdu8311TempSensor
.62.1.6.1.1.2.x
Integer32
RO
actual temperature
pdu8311HygroSensor
.62.1.6.1.1.3.x
Integer32
RO
actual humidity
pdu8311InputSensor
.62.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
pdu8311AirPressure
.62.1.6.1.1.5.x
Integer32
RO
actual air pressure
pdu8311DewPoint
.62.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
pdu8311DewPointDiff
.62.1.6.1.1.7.x
Integer32
RO
Summary of Contents for Expert PDU Energy 8311 Series
Page 2: ...2 Expert PDU Energy 8311 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 22: ...Configuration ...
Page 44: ...Specifications ...
Page 75: ...Support ...
Page 80: ...80 Expert PDU Energy 8311 2021 GUDE Systems GmbH Index Timer 34 Timer Configuration 34 TLS 53 ...