57
Expert PDU Energy 8311
© 2021 GUDE Systems GmbH
Specifications
commands sent at the beginning can appear as interfering characters in the command
line (partially invisible).
Editing
The following edit functions are available when the terminal supports VT100, and Raw
Mode is deactivated. Entered characters are inserted at the cursor position.
Keys
Function
Left, Right
moves cursor left or right
Pos1, End
moves cursor to the beginning or end of line
Del
deletes character under the cursor
Backspace
deletes character left of cursor
Up, Down
shows input lines history
Tab, Ctrl-Tab
completes the word at cursor
Ctrl-C
clears the line
Sensor Examples
a) External Sensors
>extsensor all show
E=1,L="7106",0="21.3°C",1="35.1%",3="1013hPa",4="5.2°C",5="16.0°C""
E=2,L="7102",0="21.2°C",1="35.4%",4="5.3°C",5="15.9°C""
The command lists one connected external sensor per line, and the individual meas-
ured values are separated by commas after the label name. The digit before the equal
sign corresponds to the Index field in the External Sensor Table.
>extsensor 1 0 value show
Displays temperature of the sensor at Port 1
b) Line Sensors
>linesensor all "0,1,2,3,12" show
L=1,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
L=2,L="Power Port",0="13000Wh",1="0W",2="223V",3="0A",12="996199s"
This command outputs all line sensor values in one line. A list of all fields (according to
the energy sensor table) is transferred as parameter. In this example these are the
fields Absolute Active Energy (0), Power Active (1), Voltage (2), Current (3) and Reset
Time (12).
>linesensor 1
"0,1,2,3,12"
show
>linesensor 1 1 show
These variants give the sensor values of the field list or of a sensor at Line-In 1.
For devices with Overvoltage Protection, the "linesensor all" command also outputs
the state of the protection ("OVP=x"). A "1" means ok, a "0" a failure of the protection.
c) Port Sensors
>portsensor all "0,1,2,3,12" show
P=1,L="Power Port",0="13000Wh",1="0W",2="225V",3="0A",12="998218s"
Summary of Contents for Expert PDU Energy 8311 Series
Page 2: ...2 Expert PDU Energy 8311 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 22: ...Configuration ...
Page 44: ...Specifications ...
Page 75: ...Support ...
Page 80: ...80 Expert PDU Energy 8311 2021 GUDE Systems GmbH Index Timer 34 Timer Configuration 34 TLS 53 ...