9
Expert PDU Energy 8311
© 2021 GUDE Systems GmbH
Device Description
Electrical Measurement Specification
Category
Range
Unit
Resolu-
tion
Inaccuracy
(typical)
Voltage
90-265
V
0.01
< 1%
Current
0 - 16
A
0.001
< 1.5%
Frequency
45-65
Hz
0.01
< 0.03%
Phase
-180 - +180
°
0.1
< 1%
Active power
0 - 4000
W
1
< 1.5%
Reactive power 0 - 4000
Var
1
< 1.5%
Apparent power 0 - 4000
VA
1
< 1.5%
Power factor
0 - 1
-
0.01
< 3%
Energy Counter
Active Energy
(total)
9.999.999,999
kWh
0.001
< 1.5%
Active Energy
(temporary)
9.999.999,999
kWh
0.001
< 1.5%
1.6
Sensor
Two external sensors can be connected to the
Expert PDU Energy 8311
. The follow-
ing sensors are currently available
Humidity/Temperature Sensor 7102 (
End-of-Life
)
Cable length
2m
Connector
RJ45
temperature range
-20°C to +80°C, ±0,5°C (maximum) and ±0,3°C (typical)
air humidity range
(non-condensing))
0-100%, ±3% (maximum) and ±2% (typical)
Summary of Contents for Expert PDU Energy 8311 Series
Page 2: ...2 Expert PDU Energy 8311 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 22: ...Configuration ...
Page 44: ...Specifications ...
Page 75: ...Support ...
Page 80: ...80 Expert PDU Energy 8311 2021 GUDE Systems GmbH Index Timer 34 Timer Configuration 34 TLS 53 ...