GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 1
Chapter 1 Product Introduction
GST5000 Intelligent Fire Alarm Control Panel (FACP) is designed by EN 54-2 standard
with qualities of simple installation, operation, and easy maintenance. It is used in fire
alarm system with the following features:
(1) It controls maximum 60 fire zones. Each zone has Alarm and FLT/Disable LEDs
and a zone label separately. It’s expandable to a maximum of 256 zones.
(2) It provides 4 Class A loops as standard, which can be expanded to maximum 28
loops. Each loop can have up to 235 addressable devices. It is compatible with a
series of addressable GST products, which are intelligent sounder strobe (I-9403)
complying with EN 54-3, photoelectric smoke detector (I-9102) complying with EN
54-7, rate of rise and fixed temperature heat detector (I-9103) complying with EN
54-5, intelligent manual call point (I-9202) complying with EN 54-11, intelligent
reflective beam detector (I-9105R) complying with EN 54-12, input and output
module (I-9300, I-9301) complying with GEI 1-084, and loop isolator (C-9503)
complying with GEI 1-052.
(3) Graphic display can show 320×240 dot matrix, assisting the 15 LEDs to display
important information.
(4) The memory does not lose data even if power supply is accidentally removed.
(5) It has manual keys for each zone, which can activate/mute the sounder strobe
separately.
(6) Automatically prompting operation steps for every alarm device and for smoke
exhaust and fire extinguisher by field programming.
(7) Sounder strobe interface provides 0.5A/24V output, compatible with GST
conventional sounder strobe (C-9403) designed according to EN 54-3.
(8) RS232 interface enables communication with PC.
(9) RS485 interface enables networking.