GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 53
Restart the control panel in this mode, it will register all devices again.
7.2 Exiting Commission Mode
Getting into the screen in Fig. 7-1 and choosing 1 "Monitoring State", the system will exit
commission mode.
7.3 Registration at Any Time
In commission state, pressing
SELF TEST
, the FACP will automatically register all the
devices again and display the information on the screen without affecting other
information.
7.4 Loop Card Disablement
In commission mode, the loop cards can be disabled with the same method as
detectors. The device type is 59. The user number is the loop number.
The disabled loop will stop bus output and stop the communication with the main board.
The “Enable” operation can cancel the disablement to the loop card.
7.5 Detector Searching
Under Commission Mode, the detectors can be forced into alarming state by keypad
operation. It will be easy to find the location of a specified detector and test the
transmission function of communication part.
The operation is the same as starting a module.
7.6 Protection of C&E Equations
There is a three-foot setting pin on the main board, putting its jumper at LEWR end
when setting up, modifying or deleting a cause and effect equation. After system
commission, you must put it at LDWRProtect end to protect the C&E equations.