GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 22
Fig. 4-6
A 4.7k
Ω
resistor is connected at the FIRE ALARM OUTPUT as factory default. Please
remove it and keep it well before connection. After connecting the loop in correct polarity,
add the resistor to the end of the line.
NOTE: Fire supervisory devices are polarized. Note polarity in connection. The
maximum current of the circuit depends on the number of fire supervisory
devices. Do not overload.
4.4.4 Connection of Class A Loop
A Class A loop is shown in Fig. 4-7.
Fig. 4-7
Note: Every loop isolator can control maximum 32 detectors.
4.4.5 Connection of Communication Loop
LOOP OUT
(XT4)
LOOP IN
(XT2)
Addressable
field devices
Addressable
field devices
Loop Isolator
Loop Isolator
Diode
Fire Supervisory
Device
End-of-line
Resistor 4.7k
Ω
Diode
FIRE ALARM
OUTPUT (XT5)
Fire Supervisory
Device