Page 41
again or if there are new alarms, the speaker will sound again.
5.7 Rules for Information Display
If there are more than one piece of information, they will be displayed in the following
order: fire alarm, action, fault, start, disablement.
①
The earliest fire alarm is displayed in priority. The latest action, fault, disabled
information is displayed in priority.
②
Fire alarm, fault, and disabled information can be displayed by both zone and loop
display modes. Start and action can only be displayed by loop mode.
③
In any display mode, the system will return to displaying message of the highest
priority if there is no operations within 20s (15s
~
30s).
5.8 Rules for Sound Indication
When there is fire alarm or fault, the speaker of the FACP will give sound indication.
The FACP gives fire truck sound when fire alarm occurs.
The FACP gives action sound when any device is activated.
Module action
――
slow “tick” sound.
Gas extinguishing device action
――
police car sound
Delay activation of devices by automatic C&E linkage
――
quick “tick” sound.
The FACP gives ambulance sound when fault occurs.
The control panel will give sound of higher priority if two types of information occur
simultaneously. Pressing
MUTE
can stop the sound; pressing
MUTE
again, the control
panel is still in mute state. It will sound by priority when new event appears.