GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 51
6.4.7 Browsing supervisory data of addressable devices
In the system setup menu as shown in Fig. 6-7, choose item 7 “Monitoring Device”,
enter setting mode of fire display, as shown in Fig. 6-14.
Fig. 6-14
Input loop number (Channel NO), code, command, intervals between two commands
(Alternation).
In the Item of “Command” of the above screen, inputting different number represents
different command. Details are as follows:
“0“ represents “polling”: Display value in “450
~
650” is normal; display value in
“900
~
1200” is fire alarm; display value in “0
~
120” is fault.
“1” represents “register”: If display value is 720, it is normal.
“2” represents “viewing dynamic data”: It can read data of detectors in real time.
It monitors commissioning state of I-9105R Intelligent Beam Detector, if the
return value is between “680
~
750”, it means the commission is successful.
”3” represents “viewing static data”.
“4” represents “immediate start of gas extinguishing devices”. If the command
of “Turn on gas release 24V”, gas-extinguishing devices will be started at once.
Please be cautious with this operation.
“5” represents “delay start of gas extinguishing devices”. If the command of
“Turn on gas release 24V”, gas-extinguishing devices will be started after a
delay of 30s. Please be cautious with this operation.
“6” represents the command of “Turn on gas release 24V”. Please be cautious
with this operation.
“7” represents “start ordinary module”, which will cause output of
corresponding modules. Please be cautious with this operation.
Ver V4.05f
Monitoring Device
Channel NO:
Code:
Command:
Alternation: