GST5000 Intelligent Fire Alarm Control Panel
Installation and Operation Manual (Generic Part)
The Intelligent Solution
Page 15
(103mm
×
57mm) on the front panel of the control panel. The printer is made up of front
cover, rack, head, circuit, spindle and scroll. There are “SEL” and “LF” keys and
indicators on the right-upper side of the front panel on the control panel, and paper-out
slot with cutting saws on lower part. The printer head is installed in the rack, and at the
bottom of the head is paper-in slot. Fix the printer on the panel with flexible bars. Place
the scroll spindle on the rack. The rack and printer can be simply pulled out or plugged
into the control panel for changing paper.
(3) Communication
Card
GST5000 Intelligent Fire Alarm Control Panel provides a multi-functional
communication port, connecting with network cards to realize networking among GST
series fire alarm control panels, to form urban fire alarm supervisory network through
public telephone network and to fulfill graphic supervision by connecting with CRT
system in the control center of buildings. The control panel watches network cards
running in real time, that is, the cards can take effect as inserted.
Note: You need to purchase a CRT card for your first order of GST5000. Only with
this CRT card, device definition and C&E equations can be downloaded from PC.
3.4 Field Devices
3.4.1 A Series of Intelligent Fire Detectors
GST 5000 can connect with a series of fire detectors, such as I-9102, I-9103, and
I-9105R. The detectors installed in the protected area transmit monitoring message to
the FACP through Class A loop. Every detector has its own address with which the
FACP can supervise the information of alarm, fault, and normal status of the detectors.
3.4.2 Modules
GST5000 can connect with I-9300 addressable input module and I-9301 addressable
single I/O module. I-9300 module receives the signal of normally open switching signal,
and transmits the information to the FACP (This type of FACP is able to activate the
connected devices). I-9301 single I/O module connects with the devices controlled by
the FACP, such as smoke exhauster, fan blower and fire valve. It can also receive the
self-answering signal.
3.4.3 Loop Isolator
Loop Isolator can disable the shorted part of loop from the whole system to ensure
normal operation of other devices and to ascertain the location of the part in fault. When
the fault is repaired, the loop isolator can automatically reset the disabled part and
include it into the system.
3.4.4 Manual Call Point
A series of manual call point (such as I-9202) can be connected with the bus of
GST5000. When fire is confirmed manually, press the glass on the MCP, alarm signal
can be sent to the FACP. After receiving the alarm signal, the FACP will show the
number and location of the MCP, and sound alarm.